One Touch™ Test Mode
To speed up installation and testing, One-Touch™ testing is provided which allows the controller functionality to be
tested at the controller or reader.
Test
Action
Normal
Operation
Hold down One-Touch™ button for less than 2
One-
seconds. Present keys, press RTE switches and
Touch™
observe LEDs.
View Mode
Automatically exits after 2 minutes.
One-
Touch™
Hold down One-Touch™ button for 2 to 4 seconds.
Active Mode
Present a key to each reader (the lock will activate).
Reader and
Press the Request to Exit switch (the lock will
Request to
activate).
Exit Test
Open the door contact.
Present a key to a reader, press the Request to Exit switch and open the
door contact simultaneously.
Auxiliary and
Lock Relays
Remove link to 0V on tamper or open circuit tamper switch.
Test
Remove link to 0V on emergency override or leave open circuit tamper
switch.
Remove the link between TAMP and 0V on the Tamper & Override
Tamper and
terminal block.
Override
Remove the link between OVRD and 0V on the Tamper & Override
Test
terminal block.
Leave One-
Hold down One-Touch™ button for less than 2
Touch™
seconds. One-Touch™ Test mode will automatically
Active Test
be timed out after 1 hour, power up or power down.
mode
Observation
Controller
System status:
GREEN flashes at
normal rate.
Green
Door status: All
LEDs off.
Green-Red-
Yellow
System status
GREEN flashes at
normal rate.
Green
Door status:
GREEN on, valid key
Green-Red-
presented to reader.
Yellow
Door status:
GREEN flashes,
invalid key presented
Green-Red-
to reader.
Yellow
Door status: RED
on, door open.
Green-Red-
Yellow
Door status:
YELLOW on, RTE
switch has been
Green-Red-
pressed.
Yellow
System status:
GREEN flashes
faster than normal.
Green
Door status:
GREEN flashes once
for SIGA, twice for
Green-Red-
SIGB.
Yellow
Door status:
GREEN flashes three
times and YELLOW
Green-Red-
is on.
Yellow
Door status:
GREEN flashes four
Green-Red-
times and RED is on.
Yellow
The appropriate auxiliary relay is activated.
Both auxiliary relays are activated.
The auxiliary relay is activated.
The auxiliary relay is activated but the door relays are unaffected.
Both auxiliary and lock relays are activated, the door opens and
the lock operates.
System status:
GREEN flashes at
normal rate again.
Green
– Page 5 of 20 –
Reader
Normal operation of the
reader.
Red
Normal operation of the
reader LED changes, e.g. if
default is red it changes to
Green
green.
Reader LED flashes once for
SIGA, twice for SIGB.
Red
Reader LED flashes three
times.
Red
Reader LED flashes four
times.
Red
Reader LED returns to
normal operation.
Red