Acqua Brevetti BravoMATIC FT030 Instrucciones De Instalacion Y Uso página 37

Ocultar thumbs Ver también para BravoMATIC FT030:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

BravoMATIC filter is received (backwashing stage). At the end of the backwashing procedure, a
signal is sent to switch off/close the devices connected to the panel.
A1.15 Other connections (optional)
BravoMATIC has 2 outputs for the solenoid valves and an input for the pressure
differential switch to be connected as follows:
Remove the rear cover by using a screwdriver, inserting it in the 2 slots, and proceed as shown in
the following figure:
under such cover there are four electrical connections:
EV (Solenoid 1): voltage-free contact for managing auxiliary equipment served by the filter
(e.g. solenoid valves, pumps, alarms, etc.). This voltage-free contact can support a maximum
load of 5A at 24V AC/DC. Caution! Since this is a voltage-free contact, this cable cannot be
directly connected to electrical loads;
Caution! In the event of an alarm, this contact is enabled
EV2 (Solenoid 2): Voltage-free contact for managing auxiliary equipment served by the filter
(e.g. solenoid valves, pumps, alarms, etc.). This voltage-free contact can support a maximum
BravoMATIC - ENGLISH
MAN139 PAGE E-12