A1.10 Upper panel
On the BravoMATIC display, it is possible to see the filter service settings and the presence of any
malfunctions or faults.
ALARM
Pressing the buttons
time.
A 1.11 Filter backwash setting
The control unit allows the setting of cleaning in two ways:
1. Day/Time interval (TIME / DATE programming)
Day: minimum 1, maximum 4 – Scheduled time: day time to set.
2. Time interval: (FIXED INTERVAL programming)
Time: minimum 1 h / maximum 96 h.
Washing starts automatically when the set time has elapsed. During the cleaning the program carries
out 1 washing cycle which involves 3 rotations of the filter cartridge (opening - closing the drain). You
can set up to a maximum of 10 cycles per wash for a total of 30 rotations.
BravoMATIC is set up by company for cleaning every 4 days at 00:00 and for 1 wash cycle with 3
rotations. During the filter washing, a LED lights up inside which allows you to see, through the slits
in the front casing, the cleanliness of the cartridge.
A 1.12 Manual backwash of the filter
To carry out a filter backwash, press the buttons
BravoMATIC - ENGLISH
Symbol
When the display is off in stand-by:
Filter properly powered
-
Filter in filtration position
-
Filter in backwashing stage and LED lighting on
-
When the display shows "ALARM":
Filter out of order, see paragraph A3
-
simultaneously, it is possible to launch a backwash cycle at any
MAN139 PAGE E-7
Filter action
Next menu\increase
Previous menu\decrease
Menu\editing\confirming
simultaneously.