Instructions
move any panel from the condensing unit.
• Remove surface dirt, leaves, fibres, etc. with
a vacuum cleaner, equipped with a brush or
other soft attachment. Alternatively, blow com-
pressed air through the coil from the inside out,
and brush with a soft bristle. Do not use a wire
brush. Do not impact or scrape the coil with the
vacuum tube or air nozzle.
If the refrigerant system has been opened, the
system has to be flushed with dry air or nitrogen
to remove moisture and a new filter drier has to
be installed. If evacuation of refrigerant has to be
done, it shall be done in such a way that no refri-
gerant can escape to the environment.
Service
panel
removal
W09 Version.
OP-LSQM014, 018, OP-MSGM018, 021, OP-
MSYM009, 012, 014, OP-MSGM012, 015
13 - Fan speed controller setting for R134a
refrigerant
Fan speed Controller
FSC type
Sr. No.
Spare part number
1
2
3
XGE-2C
061H3144
4
5
6
14 - Warranty
Always transmit the model number and serial num-
ber with any claim filed regarding this product.
The product warranty may be void in following
cases:
• Absence of nameplate.
• External modifications; in particular, drilling,
welding, broken feet and shock marks.
• Compressor opened or returned unsealed.
6 | © Danfoss | DCS (CC) | 2017.11
OP-MSYM018, OP-LSQM026 - 034 - 048 - 068
- 074, OP-MSYM018 - 024 - 026 - 034, OP-
MSXM034 - 044 - 046 - 057, OP-MSGM026 -
033, OP-LSQM067 - 084 - 098, OP-MSXM068
- 080 - 093 - 099 - 108
procedure
for
Refrigerant
letter
Q
H
X
Y
G
X
• Rust, water or leak detection dye inside the
compressor.
• Use of a refrigerant or lubricant not approved
by Danfoss.
• Any deviation from recommended instructions
pertaining to installation, application or main-
tenance.
• Use in mobile applications.
• Use in explosive atmospheric environment.
For Refrigerant
R404A/R452A/R507
R404A/R507
R404A/R507/R134a/R407A/
R407F/R448A/R449A
R404A/R507/R449A
R134a
If refrigerant used is R134a
Step 1: Pull the cap from the isolator switch
using screw driver.
Step 2: Unscrew the isolator switch from the ser-
vice panel.
Step 3: Take out the isolator switch.
Step 4: Follow the same procedure you would
follow for slim pack for removing the service
panel.
Factory
Action required
setting
15 bar
360°=1 turn = Approx 0.8 bar
15 bar
(Clockwise rotation =
Increase pressure setting,
15 bar
Counter clockwise rotation =
Decrease pressure setting)
15 bar
8 bar
Rotate the screw by 9 turns in counter
15 bar
clockwise direction to reach 8 bar
• No model number or serial number transmit-
ted with the warranty claim.
15 – Disposal
Danfoss recommends that condensing
units and oil should be recycled by a
suitable company at its site.