6. Faults

6. Faults
Personnel: Skilled electrical personnel
EN
6.1 Dial markings and LED status
Dial status
40
10
Power
20
5
316L
316L
4
mA
%
0
40
10
Power
20
5
316L
316L
4
mA
%
0
12
CAUTION!
Physical injuries and damage to property and the environment
If faults cannot be eliminated by means of the listed measures, the
instrument must be taken out of operation immediately.
Ensure that there is no longer any signal present and protect against
being put into operation accidentally.
Contact the manufacturer.
If a return is needed, please follow the instructions given in chapter 8.1
"Return".
For contact details see chapter 1 "General information" or the back page
of the operating instructions.
Description
Power LED lights up green.
Pointer is within the scale.
60
Analogue output is in the
15
range of 4 ... 20 mA
80
20
100
Power LED flashes green.
Pointer is below the scale.
60
Analogue output in the range
15
of 4 ... 20 mA
80
20
100
WIKA operating instructions indicator for panel mounting, model 910.70

Operating status

Normal operation
After switching on the analogue
display, an initialisation process
is performed. Wait 5 seconds.