For the correct connection of the control, use:
1. Gauge of the cables: 0.5 mm² (20 AWG) to 1.5 mm² (14 AWG).
2. Maximum torque: 0.5 N.m (4.50 lbf.in).
3. Wiring of the connector of the control board with shielded cable and separated from the
other wiring (power, command in 110 V / 220 Vac, etc.), according to
Separation Distance on page
in perpendicularly among them, keeping the minimum separation distance of 5 cm at the
crossing point. Connect the shield according to the figure below:
Inverter
4. Relays, contactors, solenoids or coils of electromechanical brake installed close to the inverters
may occasionally generate interference in the control circuitry. To eliminate this effect, RC
suppressors (with AC power supply) or freewheel diodes (with DC power supply) must be
connected in parallel to the coils of these devices.
5. When using the external HMI (refer to
connects to the inverter must be separated from the other cables in the installation, keeping
a minimum distance of 10 cm (3.95 in).
24. If those cables must cross other cables, it must be done
side
Figure 3.3: Shield connection
chapter 7 ACCESSORIES on page
Installation and Connection
item 3.2.6 Cable
Insulate with tape
Do not ground
39), the cable that