INSTALLATION DIAGRAM OF INDOOR AND OUTDOOR UNITS

INSTALLATION DIAGRAM OF INDOOR AND OUTDOOR UNITS
Flat head
wood screw
7
Battery
cover
#
"
Flat head
wood screw
Batteries
3
Filter
Flat head
wood screw
2
Wireless remote control
The provided Remote Controller is a wireless
type, which also can be used as a wire.
Please see "How to Connect The Remote
Controller for Wired Operation", in case of
wired control is required.

Optional Installation Parts

Part
Parts name
code
Refrigerant piping
Liquid side : Ø6.35 mm
A
Gas side
: Ø12.70 mm
Pipe insulating material
B
(polyethylene foam, 8 mm thick)
Putty, PVC tapes
C
Refrigerant piping
must be protected
from physical
damage.
Install a plastic
5
cover or equivalent.
7
4
Remote control holder
Hook
1
Vinyl tape
Apply after carrying
out a drainage test.
Extension drain hose
(Not available, provided
by installer)
Fixing bolt arrangement of outdoor unit
• Secure the outdoor unit with fi xing bolts and nuts if the unit is likely to be
exposed to a strong wind.
Q'ty
• Use Ø8 mm or Ø10 mm anchor bolts and nuts.
• If it is necessary to drain the defrost water, attach drain nipple $ and cap
water proof % to the bottom plate of the outdoor unit before installing it.
One
each
108 mm
28 mm
1
One
each
Air outlet
600 mm
RAS-18, 22J2AVSG-E
w When using a multi-system outdoor unit, refer to the installation manual
provided with the model concerned.
6
For the rear left, bottom left and left piping
Installation
plate
Cut out a piece of SPACER from indoor
unit packaging box, roll it and insert
between the indoor unit and wall to tilt
the indoor unit for better operation.
The auxiliary piping can be connected to
the left, rear left, rear right, right, bottom
right or bottom left.
Shield pipe
Right
Rear
right
Do not allow the drain hose to get slack.
Make sure to run the drain hose sloped
downward.
Insulate the refrigerant pipes separately
with insulation, not together.
Saddle
8 mm thick heat resisting
polyethylene foam
125 mm
Air inlet
29 mm
90 mm
Drain outlet
Wall
Left
Bottom
Rear
right
left
Bottom left
Cut the piping
hole sloped
slightly.
125 mm
Air inlet
108 mm
Ø25 mm
Air outlet
99 mm
600 mm
Drain outlet
RAS-24J2AVSG-E