• If the second attempt to start the generator is not successful, a third (and final) attempt will begin after
approximately 8 seconds. The controller will keep the starting motor engaged for up to 2.1 seconds. The
following message appears on controller screen:
• If the third attempt to start the generator is not successful, the controller will cancel the start-up process and
the generator will go into alarm mode, displaying the following message:
ATENÇÃO
TIC" mode and enter "MANUAL"
• If the start-up has been successful, the controller will transfer the loads to the generator, sending power to
the output and displaying the following message:
• In operation, the system will monitor the electric parameters on the generator (voltage, current, and fre-
quency). If any of these parameters go outside the limit or range specified and the protection for the parame-
ter is turned on, the controller will turn off the generator, entering into protection mode and displaying the
corresponding alarm on the screen.
• If the electric grid reestablishes the power for more than 5 uninterrupted seconds, the controller will turn
off the generator, transferring the electric connection and the loads to the conventional electric grid. The
following message appears on the controller screen:
• The generator will remain on for another 20 seconds after the transfer of the load on the ATS. During this
period, if the power supply of the electric grid is interrupted, the generator can take on the load. After this
time, the generator will be turned off by the controller, going into automatic mode if no alarm occurs, repe-
ating the cycle if necessary.
STARTING FAILED!
In the event of any alarm detected by the controller, the generator will exit "AUTOMA-
Generator with powered
AUTOMATIC MODE
External power grid with
power (generator off)
3 Starting
Please wait...
ATTENTION!
output!
91