7 – Wiring
(continued)
7-8 AC Input/Output Wiring (Parallel UPS – Single Input)
Parallel Redundancy Warnings:
The total input cable length must be equal to the total
output cable length in order to prevent unbalanced load
sharing between two UPS systems under reserve mode
(i.e. IP1 + OP1 = IP2 + OP2; deviation must be <10%).
Parallel redundancy only supports 2 UPS systems (1+1
redundancy ). Do not attempt to link more than two UPS
systems via parallel redundancy.
The UPS systems must have the same rating and capacity
for parallel redundancy installation. Attempting to link
dissimilar UPS systems will damage the UPS systems
and create a serious risk of personal injury and property
damage.
Follow the steps in
Section
1
in the diagram.
2
Connect the included parallel redundancy cable
redundancy port
of each UPS system.
B
7-7, wiring the UPS systems as shown
to the parallel
A
AC I/P
IP1
UPS1
Main I/P
IP2
UPS2
Main I/P
1
B
2
21
OP1
O/P
Parallel Port
Load
O/P
OP2
Parallel Port
B
A
1
2
3
4
5
6
7
8
9
10
11
12
13
14