PARAMETER
VALUE
ShAd
no
F.ShA
0 - 100
i.ShA
0 - 100
CoSt
no
APCh
Ch
AP
Co.tE
no
rESi
Foto
DESCRIPTION
Shaded area of the photocell
In some installations due to the garage, it is possible that the door
gets in front of the photocells, interrupting the beam. If this is the
case, the door cannot complete the closing cycle.
With this function, it is possible to temporarily disable photocells
during the closing phase, so as to allow clear passage of the door.
The photocells are deactivated when the door exceeds the stroke
F.ShA
percentage set for the
re-activated when the door exceeds the stroke percentage set for the
i.ShA
limit (start of shaded zone).
The limits of the shaded area are set automatically during the self-
learning cycle (Chapter 12), as the function has been previously
enabled by setting any value for the
0
(including
).
m
NOTE: this function can only be activated if the following
conditions are met:
• encoders or limit switches must be enabled
• if the limit switch is enabled, the START ON OPENING must be
St.AP
disabled (
parameter =
m
WARNING: Improper use of this function can affect the
safety of using the automation. V2 recommends:
• Use this function only when the passage of the door in front of the
photocell really is inevitable.
• Set the closest possible shaded area limits
Function deactivated
End of the shaded area: the photocells are deactivated when the
door exceeds the stroke percentage set (
open)
Start of the shaded area: the photocells are re-activated when the
door exceeds the stroke percentage set (
open)
Sensitive Rib Input
This menu allows input to be enabled for the sensitive ribs
Input disabled
Input enabled in opening and closure
Input enabled during the closing and disabled during the opening
Input enabled during the opening and disabled during the closure
Test of the safety edges
This menu allows setting the method of control of the safety edges
working
Test disabled
Test enabled for conductive rubber safety edges
Test enabled for optical safety edges
limit (end of shaded area) and are
i.ShA
F.ShA
and
limits
no
)
0
100
= door closed /
0
100
= door closed /
- 51 -
AntE SCor
no
no
= door
= door
no
no
no
no
MEMO