Override Time. Sets time that the zone will resume the selected away mode when the user touches the
o
thermostat screen during an away period. Values: 10 to 120 minutes in steps of 10 minutes. By default, 60
minutes.
·
Auxiliary Heat. This menu is used to enable/disable the auxiliary heat. By default, the auxiliary heat is disabled. When
auxiliary heat is enabled, the following parameters are used to configure the operation of the auxiliary heat:
ES
EN
Configuration Menu.
Available Stages. Defines how many stages of auxiliary heat a system has.
o
FR
First Supply Heat. If the setting for Auxiliary heat is 1 or 2, then the first system to supply heat must be defined
o
as either: Heat Pump or Aux. Heat.
IT
Fan Configuration. Select between Electric (Fan on) or Furnace (Fan off) option. If you select Electric option,
o
define:
PT
DE
First Stage Menu.
First Stage Differential. Temperature that the system has to surpass to activate the first stage of auxiliary
o
heat. Values: 1 to 5˚C in increments of 0.5˚C. By default, 1˚C.
First Stage Hysteresis. Defines the hysteresis for the operation of the first stage. Values: 0.5-1˚C in increments
o
of 0.5˚C. By default, 0.5˚C.
Min. Time Exhausted. Minimum time that the first supply heat must be active before the first stage of
o
auxiliary heat can be activated. Possible values are 0, 45, 60 and 120 minutes. By default, 45 minutes.
Second Stage Menu.
Second Stage differential. Temperature that the system has to surpass to activate the second stage of
o
auxiliary heat. Values: 1 to 5˚C in increments of 0.5˚C. By default, 1˚C.
Second Stage Hysteresis. Defines the hysteresis for the operation of the second stage. Values: 0.5-1˚C in
o
increments of 0.5˚C. By default, 0.5˚C.
Min. Time Exhausted. Minimum time that the first stage must be active before the second stage of auxiliary
o
heat can be activated. Possible values are 0, 45, 60 and 120 minutes. By default, 45 minutes.
·
Autochange. This option allows the user to configure the three values that define the auto-changeover operation that
sets the mode of the indoor unit.
Setpoint Differential. Defines the minimum differential between heating and cooling set points. For
o
example, if set to 1˚C, the system will force the cooling set point at least one degrees higher than the heating
set point. Values: 0 to 3.5˚C in increments of 0.5˚C, by default 1˚C.
Mode Switching Protection (min). Defines the minimum run time before allowing a mode change. Possible
o
values are 15, 30, 60 and 90 minutes. By default, 30 minutes.
Heat OVR Temp. If a zone has a higher heating demand than this temperature, the system reverts heating
o
operation even if the cooling global demand exceeds the global heat demand. Possible values are: Off, 1.5 to
4˚C in increments of 0.5˚C. Default value: Off.
·
Room Temperature. This option allows the room temperature and relative humidity to be shown/hidden. By default,
the room temperature is shown.
·
Lite Step. This option configures the temperature increments (1˚C or 0.5˚C) of the base set-point for the Lite
Thermostat. By default, 0.5˚C.
·
Remote Assistance. This option enables/disables remote assistance. By default, remote assistance is disabled.
34
Fan Delay (s). Defines the delay time (in seconds) to turn off the fan when there is no demand from
§
the Auxiliary Heater. Possible values are 0, 45, 60 and 120 seconds.