Emerson FloBoss 103 Instrucciones De Seguridad Para De Uso página 7

Ocultar thumbs Ver también para FloBoss 103:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 9
Safe Use Instructions - FloBoss 103
Default values for all parameters exist in the
firmware of the FloBoss. If the default is acceptable
for your application, it can be left as it is. Perform
adjustments to the FloBoss through the
configuration software. Refer to the ROCLINK 800
Configuration Software User Manual (Form A6121).
8. The calibration routines support 5-point
calibration, with the three mid-points calibrated in
any order. The low-end or zero reading is calibrated
first, followed by the high-end or full-scale reading.
The three mid-points can be calibrated next, if
desired. The diagnostic analog inputs—logic voltage
(E1), battery voltage (E2), and board/battery
temperature (E5)—are not designed to be
calibrated.
With the optional I/O termination points installed, the
Analog Input can be calibrated using ROCLINK 800
software.
The built-in inputs that are supported with the 5-point
calibration are:
Differential pressure located at AI Point A1.
Static pressure located at AI Point A2.
RTD temperature located at AI Point A3.
These inputs are assigned to the first three Analog
Input points. The calibration procedure for these
inputs is described in the ROCLINK 800
Configuration Software User Manual (Form A6121).
9. To troubleshoot problems with the FloBoss 103,
identify whether the problem is with the configuration
or the hardware. Check the configuration in
ROCLINK 800 software to identify any incorrect
settings. Inspect the hardware for damage. Inspect
the termination boards for connection location
errors.
If you are experiencing problems with the FloBoss
103 that appear to be software related, try resetting
the FloBoss with a Warm Start, Cold Start, or
Jumper Reset.
If you are experiencing problems that appear to be
hardware-related, verify the wiring. If you still
experience problems, contact your local sales office
for return authorization.
All manuals and user guides at all-guides.com
During operation, the FloBoss 103 can be monitored
(to view or retrieve current and historical data) either
locally or remotely. Local monitoring is accomplished
either by viewing the LCD panel detailed in Section
2, or by using ROCLINK 800 software on a PC
connected through the LOI port. Remote monitoring
is performed through Comm 1 or Comm 2 of the
FloBoss using ROCLINK 800 software, or host
system. Refer to Figure 4 for the communication
terminations.
10. To remove the FloBoss 103 from operation.
disconnect power from the unit and then remove all
external wiring connections. Remove the gas lines.
Finally remove the FloBoss housing from the
pipestand or orifice plate. The FloBoss may be
placed in a box for transportation.
Form A6150
Page 5
Tabla de contenido
loading

Tabla de contenido