With regard to 6.3.3 Set-up main menu - Input set-up
User-defined inputs
In addition to the specific inputs for flow, pressure and temperature, three inputs are available that
are freely scalable. In other words, the unit can be freely defined for these inputs.
The user-defined inputs offer the following functionalities
• Calculation of the current value (with reference to a time basis)
• Totalizers (integrated current values)
• Output of the current values and totals at the analog output and/or pulse output
• Limit value functionalities with relay output
• Configurable alarm response (in line with the other inputs)
Caution!
The user-defined inputs cannot be assigned to any application, i.e. they can only be used indepen-
dently. The defined unit is the basis for scaling, displaying the current value and the totalizer0
Example: user-defined input for measuring the current, configured with the Readwin
2000 operating software
1.
Select Inputs/User-defined inputs and give the input a specific name, e.g. current meter. For
more information, see the graphic
2.
Define the signal type, time basis, unit.... In this example, the current pulse is totaled in kWh
(=3600 kJ) at the totalizer and the current value is displayed with reference to the time basis
i.e.kWh/s (=kJ/s = kW).
3.
Show the current value and totalizer on the display (Set-up/Display/Group....) and define the
outputs where necessary.
®