146 68
CARACTÉRISTIQUES TECHNIQUES
TECHNICKÉ PARAMETRE - TECHNISCHE DATEN -
TECHNICAL CHARACTERISTICS - TECHNISCHE DATEN -
CARATTERISTICHE TECNICHE - TECHNISCHE EIGENSCHAPPEN -
CARACTERÍSTICAS TÉCNICAS - CARACTERÍSTICAS TÉCNICAS
D
GENAUIGKEIT
Genauigkeit bei der Wirkenergie:
Genauigkeit bei der Blindenergie:
CE-KENNZEICHNUNG
The 146 68 product complies with :
The requirements of the European directive on electromagnetic compatibility (EMC) no. 89/336/CEE dated 3 May 1989,
modi ed by directive no. 92/31/CEE dated 28 April 1992 and by directive no. 93/68/CEE dated 22 July 1993.
Low voltage directive no. 73/23/CEE dated 19 February 1973, modi ed by directive no. 93/68/CEE dated 22 July
1993, modi ed by directive no. 2006/95/CE.
ELEKTROMAGNETISCHE VERTRÄGLICHKEIT
Immunity to electrostatic discharges:
Immunity to radiated radio-frequency elds:
Immunity to electrical fast transients/bursts:
Immunity to surge immunity:
Immunity to conducted disturbances:
Immunity to power frequency magnetic elds:
Conducted and radiated emissions:
Immunity to voltage dips and short interruptions:
KLIMA
Operating-temperature range:
Storage temperature range:
Humidity:
Salt mist:
SCHWINGUNGEN
Vibration from 10 to 50 Hz :
ISOLATION
Installation category:
Degree of pollution:
Rated impulse withstand voltage:
Front face:
ELectric safety:
MERKMALE DES PMD
Merkmale
(Eventuelle) Funktion zur Ermittlung der
Stromversorgungsqualität
Klassi zierung des PMD
Temperatur
Feuchte + Höhe
Betriebsleistungsklasse der Wirkleistung oder
der Wirkenergie (wenn Funktion verfügbar)
46
146 68 - Ref.: N292510/00
IEC 62053-22 Klasse 0,5S
IEC 62053-23 Klasse 2
IEC 61000-4-2 - Level III
IEC 61000-4-3 - Level III
IEC 61000-4-4 - Level III
IEC 61000-4-5 - Level III
IEC 61000-4-6 - Level III
IEC 61000-4-8 - Level III
CISPR11 - Klasse A
IEC 61000-4-11
IEC 60068-2-1/IEC 60068-2-2
-10 °C to +55 °C
IEC 60068-2-1/IEC 60068-2-2
-20 °C to +85 °C
IEC 60068-2-30 - 95 %
IEC 60068-2-52 - 2,5 % NaCl
IEC 60068-2-6 - 2 g
III (480 VAC ph /ph)
2
IEC 60947-1 - V imp: 4 kV
Klasse II
IEC 61010-1
IEC 61557-12 KONFORMITÄT Edition 1 (08/2007)
Beispiele möglicher
Kennwerte
Zusätzliche Merkmale
-
SD
K55
-
0,5
-
-
-
-
-