Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

HM700ATX
ELECTRODE STEAM HUMIDIFIER REPLACEMENT TRANSFORMER
NOTE: This kit includes one replacement transformer
(model HM700ATX/U) intended only for use with
the HM700A1000 electrode humidifier.
CAUTION
Before Servicing
1. Disconnect main power source before accessing
internal compartments.
2. The plumbing and electrical compartments contain
high voltage components and wiring. Access should
be limited to licensed HVAC professionals only.
3. During and following operation of the humidifier, the
steam components in contact with the steam such
as the cylinder, steam lines, steam distributors, and
condensate lines can become hot and burn if
touched. Please consult HM700 Installation manual
for reference.
4. Installations of humidity equipment installed by
unqualified personnel or the use of non-Honeywell
parts and components will void warranty.
Included in the Box
• Transformer
• Philips Screw
• Installation Manual
To Replace the Transformer
1. Shut off water supply to the unit.
2. Open the external disconnect and lock it out using safe
work practices.
3. Test to verify supply voltage is no longer present on the
transformer or primary terminal block.
4. Within the electrical compartment, take note of the
transformers Primary / Secondary orientation and wire
terminations.
5. Disconnect the transformer's electrical connections and
the screws connecting it to the cabinet.
For more information on maintenance and replacement, please visit http://yourhome.honeywell.com
or call 1-800-468-1502 or 1-800-814-9452
INSTALLATION INSTRUCTIONS
6. Remove the old transformer.
7. Place the new transformer where the old one was
matching the Primary and Secondary side orientation.
8. Secure the transformer using the new mounting
equipment.
9. Connect the electrical components following your unit's
wiring diagram located on the front cover of the
humidifier. Ensuring that the transformer and electrical
connections are securely fastened. Note this
transformer has multiple leads or connections. Refer to
label on the transformer to ensure you are connecting to
the proper voltage lead or connection per your unit
voltage. Ensure no bare wires are exposed or can be
shorted out.
10. Restart the unit as per the start-up instructions in the
Installation and Operations Manual provided with your
humidifier.
COVER SCREWS
M35847
Fig. 1.
TRANSFORMER
M35848
33-00164EFS-01
loading

Resumen de contenidos para Honeywell HM700ATX

  • Página 1 Primary / Secondary orientation and wire M35848 terminations. 5. Disconnect the transformer’s electrical connections and Fig. 1. the screws connecting it to the cabinet. For more information on maintenance and replacement, please visit http://yourhome.honeywell.com or call 1-800-468-1502 or 1-800-814-9452 33-00164EFS-01...
  • Página 2 MF35847 4. Dans le compartiment électrique, notez l'orientation des Fig. 2. côtés primaire et secondaire du transformateur et les terminaisons des fils. Pour plus d'informations sur l'entretien et le remplacement, veuillez visiter http://yourhome.honeywell.com ou appeler le 1-800-468-1502 ou le 1-800-814-9452.
  • Página 3 4. Dentro del compartimiento eléctrico, tome nota de la orientación primaria y secundaria de los MS35848 MS35847 transformadores y las terminaciones de los cables. Fig. 3. Para obtener más información sobre el mantenimiento y el reemplazo, visite http://yourhome.honeywell.com o llame al 1-800-468-1502 o al 1-800-814-9452.
  • Página 4 HM700ATX Automation and Control Solutions Honeywell International Inc. 1985 Douglas Drive North ® U.S. Registered Trademark Golden Valley, MN 55422 © 2016 Honeywell International Inc. 33-00164EFS—01 M.S. 03-16 customer.honeywell.com Printed in United States...