HM700A1000 Electrode Steam Humidifier
QUICK INSTALLATION GUIDE
TOOLS & SUPPLIES NEEDED
• Screwdriver
• Wrench
• Pliers
MOUNTING
Requirements
• Wall mount, minimum of 24 inches above floor.
• Unit must be level.
• Location must have ambient temp between 41° and 104° F.
• Location must have relative humidity of 5-95%.
• Allow 36 inch front clearance.
41˚ - 104˚ F
(5˚ - 40˚ C)
5-95%
24" (61 cm) minimum
Mounting Process
1. Preparation: use #8 screws at least 2" (5 cm) in length. Mount on 2x4 studs
(or stronger) vertical surface.
2. Install the rst screw at least 43.5 in. above the oor. Leave 1/4" (6 mm) of the
shaft exposed for hanging the unit.
1/4" (6 mm)
43.5" minimum above floor
3. Hang unit from top screw using the key-hole on back and ensure it is level.
4. Secure unit with second screw driven through hole at bottom.
This is a legacy product document
supported by Resideo. It is no
longer manufactured
• Shut-off water valve
• Water line (LDPE or Copper)
As close as possible to
steam distributor.
M36301
M36302
+
M36303
M36304
PLUMBING
Supply Requirements
• Use potable water;
• DO NOT use reverse osmosis or de-ionized water.
• Pressure: 30-100 PSI;
• Conductivity: 125-1250 microsiemens;
• Temperature: 34-68° F (1-20° C).
Supply Plumbing
Use 1/4" compression fitting
(included) to connect water
supply line to unit (LDPE plastic
or copper).
Connect to 1/2" OD Copper or
plastic supply line, 4 feet (or
less) from humidifier.
Always install a water shut-off valve and
coupler to facilitate future servicing.
Drain Line Installation Process
M36305
1. Attach drain hose elbow/reducer to drain
canal using supplied hose clamp.
2. Attach drain hose to reducer using
supplied spring clamp.
3. Route drain line to a oor drain and ensure
it is sloped to provide easy draining.
M36305
M36306
33-00162EFS-03
Tabla de contenido
loading

Resumen de contenidos para Honeywell HM700A1000

  • Página 9: Herramientas Ysuministros Necesarios

    Humidificador de vapor de electrodos HM700A1000 GUÍA DE INSTALACIÓN RÁPIDA HERRAMIENTAS Y PLOMERÍA SUMINISTROS NECESARIOS Requisitos de suministro • Use agua potable; • Destornillador • Válvula de cierre del paso del agua • Llave inglesa • Tubería de agua (polietileno de baja •...
  • Página 10: Electricidad

    Humidificador de vapor de electrodos HM700A1000 ELECTRICIDAD Cableado de alto voltaje Requisitos • El humidificador DEBE estar conectado a un circuito de interruptor de circuito de falla de conexión a tierra (ICFT). • Se requiere circuito de 15 amp, 120/240 voltios.
  • Página 11: Cableado De Control

    Para los detalles de otras configuraciones de cableado, consulte el manual del producto. Honeywell recomienda que en todas las instalaciones se utilice la comprobación de aire para verificar que el vapor solo se distribuya cuando el ventilador esté activo.

Tabla de contenido