Economy Mode Setup; Alarm Setup - Tripp-Lite SmartOnline SUINT1000XLCD El Manual Del Propietario

Ocultar thumbs Ver también para SmartOnline SUINT1000XLCD:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 32
6. UPS Setup and Configuration

6.6 Economy Mode Setup

ECONOMY MODE is a UPS setting that enables enhanced efficiency and reduced BTU output by suspending double-conversion
circuits whenever input power is already of sufficient quality to run connected equipment. If enabled, the UPS will run in
economy mode when the voltage is within ±10% of nominal. If the voltage goes beyond the ±10% range, the UPS returns to
on-line mode.
Note: Economy Mode is off by default.

6.7 Alarm Setup

The ALARM screen gives the user the ability to permanently enable or disable the UPS system's audible alarm in case of
an alarm event. The factory default of ON is ideal for most applications. Certain applications may require the alarm to be
disabled, in which case the OFF option may be selected.
Press the
button
for 0.1 second
Press the
for 0.1 second
Press the
button
for 0.1 second
Press the
for 0.1 second
Press the
for 0.1 second to
advance to the next
setup screen
Default
Setting
Press the
for 0.1 second to
button
advance to the next
setup screen
Set ECO
ON
Press the
for 0.1 second to
advance to the next
setup screen
Default
Setting
Press the
for 0.1 second to
button
advance to the next
setup screen
Set Disable
22
button
button
button
button
Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Smartonline suint2000xlcdSmartonline suint3000xlcd

Tabla de contenido