ABB PowerValue 11 RT G2 Guía De Inicio página 19

Ocultar thumbs Ver también para PowerValue 11 RT G2:
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 72
Troubleshooting
Alarm and events indicate warnings
and notify of errors or potential
failures in the system. The output of
the UPS is not necessarily affected
in case of an alarm but taking the
Alarm or Event
Battery mode
Battery (Orange) LED is on.
1 beep every 4 seconds.
Code: E062
Battery low
Battery(Orange) LED is On.
1 beep every 1 second.
Code: A012
No battery
Fault (Red) LED is Flash
1beep every 1 second
Code: A011
Bypass mode
Bypass (Orange) LED is on.
Code: E060
Power overload
Fault (Red) LED is Flash
2beep every 1 second
Code: A041
T R O U B L E S H O OT I N G
Possible cause
A utility failure has occurred
and the UPS is in battery
mode.
The UPS is in battery mode
and the battery is running
low.
The batteries are
disconnected.
An overload or a fault has
occurred, or a command has
been received and the UPS is
in bypass mode.
Power requirements exceed
the UPS capacity.
correct actions may prevent loss of
power to the load. If the UPS system
does not operate correctly, attempt
to solve the problem using the
table below.
Remedy
The UPS is powering the
equipment with battery
power. Prepare your
equipment for shutdown.
This warning is approximate,
and the actual time to
shutdown may vary
significantly.
Depending on the UPS load
and number of extended
battery modules (EBMs), the
"Battery Low" warning may
occur before the batteries
reach 20 percent capacity.
Verify that all batteries are
properly connected. If the
condition persists, contact
your service representative.
Equipment is powered but
not protected by the UPS.
Check for one of the
following alarms: over
temperature, overload or UPS
failure.
Remove some of the
equipment from the UPS. The
UPS continues to operate,
but may switch to bypass
mode or shut down if the
load increases.
The alarm resets when the
condition becomes inactive.
19