WARNING
WARNING
INSTALLATION
DANGER
DANGER
DANGER
DANGER
DANGER
DANGER
P O W E R VA L U E 1 1 R T G 2 6 - 1 0 K VA Q U I C K G U I D E
RELEASED ELECTROLYTE IS HARMFUL TO THE SKIN AND EYES.
REPLACE BATTERIES WITH THE SAME NUMBER AND SAME TYPE OF
BATTERIES.
DISPLAY A WARNING LABEL ON ALL PRIMARY POWER ISOLATORS INSTALLED
REMOTE FROM THE UPS AREA TO WARN ELECTRICAL MAINTENANCE
PERSONNELS THAT THE CIRCUIT FEEDS A UPS.
MAKE SURE THAT WARNING LABEL CONTAINS THE FOLLOWING TEXT OR
EQUIVALENT: "ISOLATE THE UPS (UNINTERRUPTIBLE POWER SUPPLY)
BEFORE WORKING ON THIS CIRCUIT".
HIGH FAULT CURRENTS (LEAKAGE CURRENTS). BEFORE CONNECTING THE
MAINS ENSURE THAT THE UPS IS GROUNDED!
DO NOT REMOVE ANY SCREWS FROM THE UPS SYSTEM OR FROM THE
BATTERY CABINET: DANGER OF ELECTRICAL SHOCK.
WHEN OPENING OR REMOVING THE UPS-COVERS YOU ARE EXPOSED TO
DANGEROUS VOLTAGES.
RISK OF BACKFEED VOLTAGE, ISOLATE THE UPS INSTALLING AN EXTERNAL
ISOLATING DEVICE BETWEEN MAINS INPUT AND UPS; BEFORE OPERATING
ON THIS CIRCUIT, CHECK FOR HAZARDOUS VOLTAGE.
TO REDUCE THE RISK OF FIRE, THE UNIT SHOULD ONLY CONNECT TO A
CIRCUIT PROVIDED WITH BRANCH CIRCUIT OVERCURRENT PROTECTION FOR:
• D CURVE 63A RATING (UPSTREAM CIRCUIT), FOR 6KVA MODELS,
• D CURVE 80A RATING (UPSTREAM CIRCUIT), FOR 10KVA MODELS.