Switch Bank
4 dip switches (S1, S2, S3, and S5) control settings for the alarm output. The fifth dip
switch (S4) is used only to test the delay settings.
Dip switches shown in OFF
(open) position.
Failsafe/Alarm Setting: S3
•
When Failsafe switch S3 is ON, it inverts the relay function, and the functioning of
S1 and S2.
Alarm
Mode
High
S3-ON
Low
S3-OFF probe uncovered
Delay Settings: S1 and S2
Use the delay function to slow the response, and compensate for turbulence or false
readings.
•
Delay potentiometer P1 can be adjusted to set a delay time from 1 to 60 seconds.
•
Two separate delay settings are controlled by S1 and S2:
- for alarm activation (alarm ON)
- for alarm de-activation (alarm OFF)
•
When switches are OFF (open) the delay is enabled.
•
The position of Failsafe switch S3 determines how S1 and S2 function.
S3-
High alarm/
ON
overfill protection
S3-
Low alarm/dry run
OFF
protection
Page 30
Pointek CLS200/300 Standard – OPERATING INSTRUCTIONS
O
1 2 3 4 5
F
F
/ROCKER DOWN
probe covered
alarm activated (ON)
alarm activated (ON)
S1-ON disables delay of alarm de-activation (alarm OFF)
S2-ON disables delay of alarm activation (alarm ON)
S1-ON disables delay of alarm activation (alarm ON)
S2-ON disables delay of alarm de-activation (alarm OFF)
delay: alarm activation
delay: alarm deactivation
failsafe/alarm
test delay settings
set-up mode / run mode
relay de-energized
relay de-energized