Circuit diagrams
Wiring: Pointek CLS300 standard
White
Black
Red
Switch bank
S1
P1
OFF
3
-
+
Sensor
Delay
L1
Sensor
status
L2
Output
status
NC
NO
K2
Notes:
-
Identification label is on underside of lid. Switch and potentiometer settings
are for illustration purposes only (refer to operation/setup in manual).
-
All field wiring must have insulation suitable for at least 250 V.
-
Relay contact terminals are for use with equipment having no accessible live
parts and wiring having insulation suitable for at least 250 V.
-
Maximum working voltage between adjacent relay contacts shall be 250 V.
-
Refer to the Instruction manual or contact Siemens representative for detailed
wiring information.
Wiring: Pointek CLS300 digital
Test input
Alarm output
solid-state switch
24 V DC/PROFIBUS PA
Notes:
Refer to the instruction manual or contact a Siemens representative
for detailed wiring information.
*Magnet activated sensor test
A magnet can be used to test the sensor without opening the lid of the
Pointek CLS300 digital version. Bring the magnet close to the test area
indicated on the enclosure. The sensor test starts and finishes
automatically after 10 seconds.
Pointek CLS300 connections
© Siemens AG 2018
P2
Trip
point
K1
GND
K4
2
1
L3
Power
1
2
3
on
Power
supply
12 to 250 V AC/DC
NO
K3
Solid state switch:
30 V DC/30 V AC
(peak),
82 mA max.
Relay contact:
8 A at 250 V AC, 2 000 VA
5 A at 30 V DC, 150 W
White
Reed
contact*
White
Red (+)
Sensor
Black (-)
Orange (f)
Power connection:
24 V DC or PROFIBUS PA bus
(not polarity sensitive).
Level Measurement
Point level measurement
RF Capacitance switches
Pointek CLS300 - Standard and Digital
Siemens FI 01 · 2018
4
4/59