CHAMP® PVML Emergency LED Luminaires for Ordinary
Location
Installation & maintenance information
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
APPLICATION
CHAMP® PVML Emergency LED luminaires are designed for harsh
and heavy industrial applications.
CHAMP PVML Emergency luminaires are not suitable for use in NEC
classified areas (Hazardous).
PVML:
Certifications and Compliances
UL standards
• Wet location, Type 4X
• UL1598, UL 1598A, UL50E, UL924
• IP66
CSA standard
• CSA C22.2 No.250.0, CSA C22.2 No. 141
WARNING
To avoid electric shock:
Be certain electrical power is OFF before and during installation and
maintenance.
Luminaire must be supplied by a wiring system with an equipment
grounding conductor.
To avoid burning hands:
Make sure lens and housing are cool when performing
maintenance.
1.
Read carefully before installing and wiring luminaire and retain
for future reference.
2.
Do not use accessory equipment not recommended by
manufacturer.
3.
Use only replacement parts from Eaton's Crouse Hinds
division.
4.
To avoid the risk of fire, explosion or electric shock, this
product should be installed, inspected and maintained by a
qualified electrician only, in accordance with all applicable
electrical codes.
5.
Do not use this equipment for other than intended use.
6.
Replace entire battery unit and LED driver when necessary.
Contact the manufacturer for information on service.
7.
Do not attempt to service battery.
8.
See product label for minimum supply wire temperature rating.
9.
Battery requires 24hrs to fully charge. Allow 24 hours charging
time before depending on the battery to operate at full
capacity.
STORAGE INSTRUCTIONS
1.
EM luminaire must be stored in an ambient temperature range
of 0°C to 40°C.
2.
Battery should be charged and discharged within 6 months.
At a minimum, the battery should be recharged within this time.
INSTALLATION
Max. mounting height: 27 feet (8.22m)
MOUNTING:
1.
Mount the cover module in its support position.
• Ceiling and wall mount: mark and drill desired location on mounting
surface. Secure with 1/4" (6mm) bolts or lag screws (not provided).
• Pendant, cone, stanchion mount: securely thread onto the appropriate NPT
size conduit. Tighten set screw located in the conduit hub. See Figure 1.
• Eaton's Crouse-Hinds series HTL thread lubricant must be added to the
conduit threads to prevent water from entering the fixture.
IF 1918 • 03/21
Copyright © 2021, Eaton's Crouse-Hinds Division
Refer to the luminaire nameplate for specific classification information,
maximum ambient temperature suitability and corresponding operating
temperature
(T code). Luminaire construction is designed for use indoors and
outdoors in marine and wet locations, where moisture, dirt, corrosion,
vibration and rough usage may be present.
Input voltage:
• 120-277 VAC, 50/60 HZ
WARNING
To avoid explosion:
Make sure the supply voltage is the same as the luminaire voltage.
Do not operate in ambient temperatures above those indicated on
the luminaire nameplate.
Use proper supply wiring as specified on the luminaire nameplate.
All gasket seals must be clean and undamaged.
Before opening, electrical power to the luminaire must be turned
off. Keep tightly closed when in operation.
Clean only with damp cloth.
IMPORTANT
10.
The emergency battery requires a minimum charge time of
one (1) hour before testing the circuit, 24 hours is required for
a full charge.
11.
Equipment should be mounted in locations and at heights
where it will not readily be subjected to tampering by
unauthorized personnel. Max. mounting height : 27 Feet
(8.22m)
12.
Do not mount near heat producing equipment.
13.
See product label for maximum ambient temperature.
14.
The emergency luminaire is intended to be installed with
CG-256 (issued by the American Bureau of Shipping and Coast
Guard.
15.
This product must be installed in accordance with the
applicable installation code by a person familiar with the
construction and operation of the product and the hazards
involved.
FIGURE 1
Set screw
FIGURE 1
IF 1918
INSTALLATION
TRUNNION/YOKE MOUNT (for direct wall mount applications with the luminaire housing having Cat. Suffix. S812 only):
1.
Trunnion mount accessory is available for use with ceiling CM2, CM3 mounts only.
2.
Adjustable for three angles as shown in figures below.
WIRE GUARD INSTALLATION
•
Loosen but DO NOT completely remove wire guard screw. If
already loosened, move to next step.
•
Set wire guard in place by pushing it over the bottom rim of
the luminaire which is on the lowest casting until it sits in place
above hat. Ensure that the wire guard is in place around the
complete bottom and is not partially in place above the rim.
•
Tighten the screw attached to wire guard until guard is
securely attached to bottom casting. The screw will be tight
enough when the wire guard can no longer easily rotate on the
luminaire.
NOTE: The sheet metal tabs which the screw goes through do not
need to be touching for the guard to be securely fastened; the wire
guard will be secure without those two tabs touching one another.
Open
hinge
Ground wires
Page 1
IF 1918 • 03/21
The wire guard Cat. No. P3001 is optional.
CHAMP LED SAFETY CABLE
1.
Pass cable through the Kwik-Loc adjustment hole in the
direction of the arrows (see Figure 3).
2.
Locate attachment point in between two (2) of the housing fins,
as shown in Figure 2.
3.
Route secondary retention cable through attachment point
on the fixture housing and back though the Kwik-Loc second
adjustment pin hole in the direction of the arrows.
4.
Connect cable to a permanent structure, or anchor (customer
supplied).
5.
Remove any slack to ensure the cable is taut and confirm
engagement of the lock.
FIGURE 2
Copyright © 2021, Eaton's Crouse-Hinds Division
FIGURE 3
Page 2