Siemens CBP Manual Del Usuario página 98

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

06.2005
X490 – Relay
outputs
X491 - Analog input
and output, digital
inputs
NOTE
Siemens AG
6SE7087-6NX84-0FF5
SIMOVERT MASTERDRIVES
The following connections are provided on the terminal strip:
♦ 1 relay output (changeover contact)
♦ 3 relay outputs (NO contact)
Terminal
Designation
38
DO13
39
DO12
40
DO11
41
DO22
42
DO21
43
DO32
44
DO31
45
DO42
46
DO41
Connectable cross-section: 1.5 mm
Terminal 38 is at the top when installed.
Table 6-3
Terminal assignment at connection X490
Terminal Designation
47
AO
48
AOM
49
AI1P
50
AI1N
51
DIM
52
P24AUX
53
DI1
54
DI2
Connectable cross-section: 1.5 mm
Table 6-4
Terminal assignment of connection X491
Terminal P24AUX supplies digital inputs DI1 and DI2. No external 24 V
supply may be connected to this terminal.The current output at terminal
P24AUX, i.e. the total outputs of all option boards, must not exceed
150 mA.
The board EB2 is designed as a PELV circuit (Protective Extra Low
Voltage). The ground of board EB2 is connected internally to earth.
Option boards
Significance
Relay output 1, NC contact
Relay output 1, NO contact
Relay output 1, reference contact
Relay output 2, NO contact
Relay output 2, reference contact
Relay output 3, NO contact
Relay output 3, reference contact
Relay output 4, NO contact
Relay output 4, reference contact
2
(AWG 16)
Significance
Analog output
Ground analog output
Analog input +
Analog input -
Ground digital input
24 V supply
Digital input 1
Digital input 2
2
(AWG 16)
EB2 – Expansion Board 2
Range
Voltage: ± 10 V, 5 mA
Current: ± 20 mA, 500 Ω
Voltage: ± 10 V, 40 kΩ
Current: ± 20 mA, 250 Ω
0 V
24 V, 150 mA
24 V, 4 kΩ
24 V, 4 kΩ
6-5
Tabla de contenido
loading

Este manual también es adecuado para:

Cbp2CbcSlbEb1Eb2Sbp ... Mostrar todo

Tabla de contenido