SELECTABLE
FUNCTION
FIELDS
"Activation of
commissioning prog."
Activation of
000/001
commissioning
program
9.12
BASIC PROGRAMMING
- Programming must be done only by a technical expert, with the engine turned off and the
ATTENTION
three-way switch turned to "MAN".
- The "Panel Vdc voltage" and "Crown teeth" parameters are set by the manufacturer of the
diesel pump and must not be modified for any reason!
- Incorrect unit programming can completely change machine operation and, in some cases,
can cause serious harm or damage and the termination of the guarantee !
Turn the switch to its "MAN" mode.
Power the electric panel and press and hold the PROG / RESET / ENTER switch for more than 5 seconds to access the
PASSWORD parameter. The cursor blinks.
Enter the 101 password and press the PROG/RESET/ENTER key to confirm
Select the function using the UP / DOWN keys and press the PROG/RESET/ENTER key to confirm.
Enter the parameter value using the UP / DOWN keys and press the PROG/RESET/ENTER key to confirm
Repeat this procedure to set each function.
FUNCTION
Set voltage DC of
starting batteries
" MP06 VDC VOLTAGE"
calibration of tachometer
" CROWN WHEEL
TEETH "
Set allarm low rpm
" LOW RPM
THRESHOLD "
Counter operation hour
" WORKING HOURS "
Activation function
weekly self
"ENABLE WEEKLY
ROUTINE"
Attivaction automatic
shut off
" ENABLE SELF STOP "
DEFAULT
VALUES
000
SELECTABLE
DEFAULT
FIELDS
VALUES
In function of
000 / 001
engine motor
model
In function of
000 / 999
engine motor
model
0000 / 9999
2500
0000 / 9999
000 / 001
000 / 001
NOTES
000 = Disabled
001 = Activation
NOTES
000= 12VDC
001= 24VDC
The indicated value is equivalent to the number of teeth
present on the ring gear of the engine where the sensor pick-
up is installed.
The value shown indicates the turns which makes
reference the alarm.
The value indicates the number of operation hours of the
-
engine motor, it can be modified in case of replacement cards.
000 = Disabled
0
001 = Activation
000 = Disabled
0
001 = Activation
120