Internal Battery Replacement

Under normal conditions, the original batteries in your UPS will last many years. See Safety section before replacing batteries. The
batteries are designed for hot-swap replacement (i.e. leaving the UPS ON), but some qualified service personnel may wish to
completely turn the UPS OFF and disconnect equipment before proceeding. It is suggested that you remove the batteries before
the installation process.
Remove the screws
1
Separate the front bezel
2
Remove the battery connector snap covers. Save
3
these covers for reuse.
Disconnect the battery connectors
4
that secure the battery retention bracket in
screws
D
place.
Remove the battery retention bracket
5
recycle the middle battery pack
Remove/recycle the side battery packs
6
Replace the battery packs
7
Re-attach the battery retention bracket
8
Replace the screws
9
bracket in place.
Connect the battery connectors
10
black-to-black, red-to-red, white-to-white and green-
to-green.
Reinstall the battery connector snap covers.
11
Replace the front bezel
12
13
Replace the screws
place.
201102161 933070.indb 28
which secure the front bezel.
A
from the front panel.
B
and remove the
C
and remove/
E
.
F
.
G
and
.
F
G
.
E
to secure the battery retention
D
. Attach connectors
C
.
B
to secure the front bezel in
A
A
1
B
2
D
C
4
5
G
6
28
13
12
D
9-10
F
E
7-8
G
7
3/29/2011 4:34:20 PM