Connection Notes
•
Before opening the lid, ensure there are no dust deposits around the SITRANS LPS200.
Ensure that the atmosphere around SITRANS LPS200 is settled.
•
Use a fuse for the signal output and power supply (max. 10 A, fast or slow, HBC,
250V).
•
Make sure the main voltage does not exceed the maximum voltage listed on the
product label and the setting of the voltage selector.
•
In case of inexpert handling or handling malpractice, the electric safety of the
device cannot be guaranteed.
•
Provide protection for relay contacts to protect the device against spikes if inductive
loads are connected.
Switching Logic (universal voltage, DPDT)
A5E34210883
SITRANS LPS200 – OPERATING INSTRUCTIONS
FSL
SPDT
7 6 5
DPDT
8 9 10
PNP
1 2 3
yellow
SPDT
7
6
DPDT
8
9
PNP
1
2
green
Power
failure
7
6
5
8
9
FSH
FSH:
Use this setting when sensor
is used as a full detector.
7 6 5
Power failure or line break is
regarded as "full" signal (pro-
tection against overfilling).
8 9 10
FSL:
Use this setting when sensor
is used as an empty detector.
1 2 3
Power failure or line break is
regarded as "full" signal (pro-
green
tection against overfilling).
Factory setting: FSL
5
7
6
5
10
8
9
10
3
1
2
3
yellow
10
1
2
3
Page EN-13