Installation Instructions – Axcent (Small & Large)
Trunnion Mount
Tools Required
#2 Phillips head screwdriver, socket wrench, 5/8" socket,
5/8" wrench, 5/16" socket, 5/16" wrench, torque wrench.
1.
The fixture comes with a wall mount wedge plate pre-
installed. Remove the wall mount wedge plate and
discard. (Figure 1.)
2.
Make wiring connections between the fixture and
trunnion per wiring diagram. Use provided outdoor-rated
wire nuts. (Figure 3.)
3.
Attach the trunnion assembly to the fixture and tighten
(2) 1/4 -20 Phillips head screws to 20 in-lbs (Figure 7).
Ensure that the luminaire supply leads are not pinched
between the wedge plate and housing.
4.
Mount luminaire to surface using the hole pattern
provided on the trunnion bracket. Hardware must be
adequate to ensure that the mount can support up to a
25 lb fixture. (Figure 8.)
5.
Loosen but do not remove the locating screws and
locking bolts and nuts shown in (Figure 8).
6.
Adjust the trunnion flood bracket to desired angle.
Retighten #3/8-16 locking bolts and nuts to 30 ft-lbs and
#10-32 locating screws to 3 ft-lbs. (Figure 8.)
Knuckle Mount (Axcent Small Only)
Tools Required
Phillips head screwdriver.
N
otee:
This configuration is equipped with an adjustable
knuckle which can be mounted directly to the 1/2"
NPS access hole in the cover plate of a junction box.
1.
The fixture comes with a wall mount wedge plate
preinstalled. Remove the wall mount wedge plate and
discard. (Figure 1.)
2.
Make wiring connections between the fixture and
knuckle mount per wiring diagram. Use provided
outdoor-rated wire nuts. (Figure 3.)
3.
Attach the knuckle mount assembly to the fixture and
tighten (2) 1/4 -20 Phillips head screws to 20 in-lbs
(Figure 9). Ensure that the luminaire supply leads are
not pinched between the wedge plate and housing.
4.
Route electrical leads through the 1/2" NPS access hole
in cover plate (supplied by others). Secure cover plate to
knuckle with lock nut and Torque 65 in-lbs. Note: Ensure
wires do not get pinched.
Do not mount the cover plate to the junction box
N
otee:
and then screw the knuckle of the luminaire into
the cover plate. This can result in twisting the wires,
causing connections to break and creating a shock
hazard when power is turned on.
5.
Use wire nuts or other approved connectors to wire
fixture per wiring diagram. (Figure 3.)
4
EATON
IB514031EN
Installation instructions
1/4-20 Screws
Torque to 25 in-lbs
(3X)Set Screw
Torque to
10 ft-lbs.
(3X)Lock Nuts
Torque to
65 in-lbs.
Figure 7. Axcent Small
Wedge Plate
#10-32 Locating
Screws
1/4-20 Lock Screws
0.37[9.5] X 0.82
[20.9](2X)
Ø 0.5"
[12.7mm]
Figure 8. Axcent (Small & Large)
Wedge Plate
Cover
#8-32 Screws
Torque to 15 in-lbs.
1/4-20 Lock Screws
Torque to 20 in-lbs.
#3/8-16 Locking
Bolts And Nuts
2.75"
[69.3mm]
1.37"
[34.7mm]
5"
[127mm]