2.2 RS-485-0
- Interface according to RS-485 standard.
- Galvanically isolated interface with a differential signal, giving greater resistance
against electromagnetic interference.
- Allows simultaneous connection of several devices with network master.
- Maximum bus length of 1000 meters.
NOTE!
For detailed information about network installation, parameterization, protocols
and operation of the CFW11 using the RS-485 interface, consult the
RS-232 / RS-485 Serial Communication Manual of the CFW11 in the
CD-ROM that goes with the drive.
4
- TX LED data transmission indication by the
inverter, green color.
- Termination resistor (S1). Switch to enable the
termination resistor necessary for the RS-485
interface. This resistor must be enabled
(with both switches S1:1 and S1:2 in the ON
position) only on the two devices located in
the of the main bus.
Table 2: Connector XC7 pins for RS-485 interface
Pin
Name
1
A-Line (-)
2
B-Line (+)
3
GND
4
Ground
XC7
Function
RxD/TxD negative
RxD/TxD positive
0V isolated from the
RS-485 circuit
Ground (shielding)