Specifications; Accuracy Specifications - WIKA SA-11 Manual De Instrucciones

Transmisor de presión para procesos estériles
Ocultar thumbs Ver también para SA-11:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

3. Specifications

3. Specifications

Accuracy specifications

Non-linearity per BFSL (per IEC 61298-2)
Accuracy
1)
Mean temperature coefficients at 0 ... 80 °C [32 ... 176 °F]
Zero point
Span
Long-term stability (per DIN 16086)
Adjustability of zero point, span
Non-repeatability (per IEC 61298-2)
Mounting position influence
1) Including non-linearity, hysteresis, zero offset and end value deviation (corresponds to measured error per IEC 61298-2), calibrated in vertical mounting position
with process connection facing downwards.
Measuring ranges, gauge pressure
Measuring range
bar
0 ... 0.25
0 ... 0.4
0 ... 0.6
0 ... 1
0 ... 1.6
0 ... 2.5
0 ... 4
0 ... 6
0 ... 10
0 ... 16
0 ... 25
WIKA operating instructions pressure transmitter, model SA-11
≤ 0.2 % of span
≤ 0.5 % of span
≤ 0.25 % of span
Measuring range 0 ... 0.6 bar to 0 ... 25 bar
Measuring range 0 ... 0.4 bar
Measuring range 0 ... 0.25 bar
≤ 0.2 % of span / 10 K
≤ 0.2 % of span/year
Adjustment is made using potentiometers inside the instrument.
Not possible for IP68 cable outlet.
≤ 0.1 % of span
Calibrated in vertical mounting position with process connection facing downwards.
psi
0 ... 5
0 ... 10
0 ... 15
0 ... 30
0 ... 60
0 ... 100
0 ... 160
0 ... 200
0 ... 300
≤ 0.2 % of span / 10 K
≤ 0.25 % of span / 10 K
≤ 0.,4 % of span / 10 K
Measuring ranges, absolute pressure
Measuring range
bar abs.
0 ... 1
0 ... 1.6
0 ... 2.5
0 ... 4
0 ... 6
0 ... 10
0 ... 16
psi abs.
0 ... 15
0 ... 25
0 ... 50
0 ... 100
0 ... 250
9
EN
Tabla de contenido
loading

Tabla de contenido