3. Specifications
Output signal
Signal type
EN
Load in Ω
4 ... 20 mA, 2-wire
0 ... 20 mA, 3-wire
DC 0 ... 10 V, 3-wire
DC 0 ... 5 V, 3-wire
Voltage supply
Supply voltage
Overvoltage protection / dielectric strength
Time response
Response time (10 ... 90 %)
1) NEC class 02 voltage supply (low voltage and low current max. 100 VA even under fault conditions)

Electrical connection

Angular connector DIN 175301-803 A
Field case
Circular connector M12 x 1 (4-pin)
Cable outlet, 1.5 m
1) The stated ingress protection only applies when plugged in using mating connectors that have the appropriate ingress protection.
Other electrical connections on request
12
4 ... 20 mA, 2-wire
0 ... 20 mA, 3-wire
DC 0 ... 10 V, 3-wire
DC 0 ... 5 V, 3-wire
Other output signals, e.g. CANopen, see product label
R A ≤ (U
- 10 V) / 0.02 A
+
R A ≤ (U
- 3 V) / 0.02 A
+
R A > 10 k
R A > 10 k
Signal type 4 ... 20 mA, 2-wire
Signal type 0 ... 20 mA, 3-wire
Signal type DC 0 ... 10 V, 3-wire
Signal type DC 0 ... 5 V, 3-wire
DC 36 V
1)
≤ 10 ms
Ingress
Wire
protection
cross-section
1)
IP65
Max. 1.5 mm
-
IP67
IP67
-
IP68
Max. 0.5 mm
WIKA operating instructions pressure transmitter, model SA-11
DC 10 ... 30 V
DC 10 ... 30 V
DC 14 ... 30 V
DC 10 ... 30 V
Cable diameter
6 ... 8 mm
2
-
-
6 ... 8 mm
2
Cable length
-
-
-
1.5 m