English
1. General Instructions
The general instructions for storage systems, material no. 103041, in the current version, must be observed.
National standards and safety regulations must be observed.
2. Fundamental safety instructions
Smoking in the vicinity of the storage system is prohibited. Fire/open flame must not
come into the contact with the storage facility.
The technical regulations TRG 280 for the storage of pressurised gas when using
pressurised gas cabinets must be observed. This regulation is concerned with the
storage of flammable or highly poisonous gas in pressurised gas cylinder containers.
TRG 280, Section 5.1.4: Dispensing pressured gas from cylinders inside the storage
facility is prohibited.
TRG 280, Section 5.1.5: Unauthorised access to the gas storage facility must be
prevented; warning signs should be displayed on the outside of the storage system.
3. Use and intended purpose
The gas cylinder cabinet is used for storing pressurised gas cylinders outdoors.
4. Technical details
Design
The gas cylinder cabinet incorporates the following features:
The cabinet complies with the European regulation TRG 280 for storing pressurised gas outdoors.
-
Sturdy steel profile frame, screwed together.
-
The roof and the rear wall are manufactured from galvanized profiled steel.
-
The lockable wing doors and the side walls are manufactured from steel mesh.
-
The 500 mm protruding roof ensures weather protection.
-
The GS 305-B with feet has a 100 mm space between the base and the floor.
-
The GS 305-B model with a base ensures that the gas cylinders can be placed directly inside the cabinet.
-
The GS 305-B model without a base allows the gas cylinders to be stored on the floor.
-
Gas cylinders can be stored individually using the rail and chain system.
-
The gas cylinders can be stored on gas cylinder pallets inside the cabinet.
-
Delivered flat pack for self assembly.
-
5. Assembly
Point of use
The liquid gas cylinder should be placed on even ground outside, the cabinet must not be accessible to
unauthorised personnel.
Do not install the cabinet near to holes, drains, drain pipes, channels, access to cellars, passageways, stairs
to buildings/outdoor facilities and emergency service access routes.
When storing flammable or toxic gases, please observe TRG 280 regulations and section 5.3 in the operating
instructions. TRG 280 stipulates that the area around the cabinet should be kept clear for a 1 m radius.
Flammable gases are classified under Ex Zone 2!
The protection area around the cabinet must not obstruct areas accessed by members of the public or
unauthorised personnel.
The cabinet must be sealed off by a wall (minimum of 2 m) on either side of the cabinet to prevent flammable
gases from escaping. The wall should offer at least 30 minutes fire resistance (TRG 280, section 5.3.3).
Gasflaschenschrank GS 305-B / GS 305
115861 / 11586
Seite 12 von 28 Seiten
Ausgabe 06/2007