Roughing-in assembly
EN
Limitations of use
EN
Observe the following limit values for installation
and operation of the system components:
Permissible ambient temperature
Installation in an electrical distribution box in a pref-
erable unscreened environment.
Installation of eSCHELL water management server
The eSCHELL water management server may only be
installed in dry interior rooms. It is solidly installed
in a distribution box on a 35 mm top-hat rail (acc.
to DIN EN 60715).
– Pay attention to good reception of the wireless
subscribers of the water management system
when choosing the installation location.
– Observe the maximum cable lengths when using
Bus extender cables.
Installation of the eSCHELL power supply
The Bus power supply unit 30 V may only be
installed in dry interior rooms. It is solidly installed
in a distribution box on a 35 mm top-hat rail
(acc. to DIN EN 60715).
It is recommended to install the power supply and
the server in the same distribution box.
Recommendation:
eSCHELL electrical distribution box
(# 00 506 00 99)
EN
0 °C to 50 °C
eSCHELL electrical distribution box (*optional)
When installing the water management server and
the power supply, the eSCHELL electrical distribu-
tion box (# 00 506 00 99) can be used as an op-
tion. With the insulation class IP65 it provides the
required protection against contact.
– Pay attention to good reception of the wireless
subscribers of the water management system
when choosing the installation location.
– Observe the maximum cable lengths when using
Bus extender cables.
– Use only the appropriate ISO terminal screw
connections for the connecting cables or the
enclosed cable bushings.
Notes on installation in the distribution box
– The bus lines must be routed with sheath up to
the terminals.
– Avoid contact of current and bus line wires, e.g.
through appropriate line routing of fastening.
– Metal distribution boxes reduce the range
of wireless signals (e.g. WLAN or eSCHELL
wireless).