Conformity:
COMPACT
European standards EN 60598-1, EN 60598-2-1, EN 60598-2-13.
FLUORE-
Community Directives 2006/95/CE, EMC 89/336 and EEC 93/68.
SCENT
IP67 protection degree (for ground recessing fittings)
IP66 protection degree (for surface mounting and suspended fittings)
Direct mounting on normally inflammable surfaces.
The luminaire must never, under any circumstances, be covered with
insulating material or the like.
The safety shields must be replaced in case of damage.
The luminaires must not be turned on without the safety shields.
Luminaires in Class II.
Use double insulated wires only or cover the wires
with the sheath provided.
Emergency luminaires.
- the preferential line must never be interrupted;
- luminous flux in emergency use: after 60 seconds, about 20% of the
-
luminous flux of the bulb in ordinary operation;
- Duration in emergency use: 2 hours for 14/21 W lamps and 1 hour for
-
28/35W lamps.
Luminaires for emergency lighting:
- power supply failure
Cables for exterior power supply should not have characteristics lower than
H07/H05 RN F and 1,5mm2 section, and the outer protection sheath must
have an external diameter between 7mm and 10mm complying with the
expected polarities:
Phase –pole F/L or terminal block 1-, Neutral –pole N or terminal block 2.
Recessed luminaires for wall mounting for both indoor and outdoor appli-
cation. The luminaires ensure a degree of protection of IP67, provided sui-
table drainage is provided for the recessed box.
Glass
temp.
Temperature on the glass below 40°C
< 40°C
Max. permis-
sible load on
Max. permissible load on the glass, in the recessed versions, is 2000 Kg
the glass
Keep these instructions carefully for future consultation.
Modifying the luminaire in any way invalidates the guarantee of conformity
L F
U
R
E
Important:
with current standards and directives.
7
E
N
G
L
S I
H