NAME
Pre-programmed
FAN FAIL
FAN FAIL
MAX INT TEMP
MAX INTERIOR TEMP
FANS PROTEC NOK
FANS PROTECTION NO OK
EMERGENCY STOP
EMERGENCY STOP
EXT TEMP ERROR
STHE COM ERROR
INT LEFT TEMP ERROR
STHI LEFT COM ERROR
INT RIGHT TEMP ERROR
STHI RIGHT COM ERROR
MAX PROCCESS TEMP
MAX PROCESS TEMP
CONTROL TEMP CHANNEL
CONTROL TEMP ERROR
ERROR
HR LEFT MAX
MAX HR LEFT REACHED
HR RIGHT MAX
MAX HR RIGHT REACHED
REMAINING WATER IN BASINS
WATER IN BASIN
AFTER T (MIN)
Pre-programmed
For exterior elements
MIN INT TEMP
MIN INTERIOR TEMP
MIN PROCCESS TEMP
MIN PROCESS TEMP
GENERAL FAIL
ALARM DISABLE FANS
English – Inglés – Inglese
DESCRIPTION
WARNING+DISABLE FANS + VALVE 0%
WARNING IN TOUCH PANEL
WARNING+DISABLE FANS + VALVE 0%
WARNING+DISABLE FANS + VALVE 0%
WARNING IN TOUCH PANEL
WARNING IN TOUCH PANEL /
Operation with the other sensor
WARNING IN TOUCH PANEL /
Operation with the other sensor
WARNING IN TOUCH PANEL
WARNING+VALVE 0%
WARNING+VALVE 0%
WARNING+VALVE 0%
WARNING+VALVE 0% OF PID OUTPUT
WARNING IN TOUCH PANEL
ACTIVATE DIGITAL OUTPUT 3 PLC
WARNING IN TOUCH PANEL
ACTIVATE DIGITAL OUTPUT 4 PLC
WARNING IN TOUCH PANEL
ACTIVATE DIGITAL OUTPUT 5 PLC
2ND ACTION
ACTION
IF BOTH : VALVE 0%
Only operation in Man
Automatically restore of
PID when HR<max
Automatically restore of
PID when HR< max
Automatically restore of
PID when water level< max
Pag. 36
EMERGENCY STOP
YES
NO
X
X
X
X
X
X
X
X
X
X
X
X