6.4.3
Intrinsically Safe FM
I.S. Class I Div 1 und Div 2, Group: A, B, C, D oppure
I.S. Class I Zone 0 AEx ia IIC T*
*Temp. Ident: T6 T
56 °C, T4 T
amb
U i / V
= 9V, I i / I
< 65,2 mA, P i = 101 mW
max
max
C i = 0,4 µF; L i = 0
Control Drawing: SAP_214 748
6.4.4
Non-Incendive FM
N.I. Class I Div 2, Group: A, B, C, D oppure
Ex nL IIC T*, Class I Zone 2
*Temp. Ident: T6 T
60 °C, T4 T
amb
U i / V
= 9V, I i / I
< 65,2 mA, P i = 101 mW
max
max
C i = 0,4 µF; L i = 0
Control Drawing: SAP_214 751
6.4.5
Intrinsically Safe CSA
I.S. Class I Div 1 und Div 2; Group: A, B, C, D oppure
I.S Zone 0 Ex ia IIC T*
*Temp. Ident T6 T
56 C, T4 T
amb
U i / V
= 9V, I i / I
< 65,2 mA; P i = 101 mW
max
max
C i < 0,4 F µ , L i = 0
Control Drawing: SAP_214 749
6.4.6
Non-Incendive CSA
N.I. Class I Div 2, Group: A, B, C, D oppure
Ex nL IIC T*, Class I Zone 2
*Temp. Ident T6, T
60 °C, T4 T
amb
U i / V
= 9V, I i / I
< 65,2 mA, P i = 101 mW
max
max
C i < 0,4 µF, L i = 0
Control Drawing: SAP_214 750
Wechsel ein-auf zweispaltig
CI/TTF300-X1
85 °C
amb
85 °C
amb
85 °C
amb
85 °C
amb
TTF300
HMI display LC tipo B
IT - 33