Fujitsu UTY-DMMUM Manual De Instalación página 5

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

(1) Remove the insulation of the remote controller cable.
55 (2-5/32)
45 (1-25/32)
30 (1-3/16)
8 (5/16)
8 (5/16)
8
(5/16)
(2) Insert the flat-blade screwdriver and remove the front
case and rear case by twisting it slightly.
Hooks (2 places)
Flat screwdriver
(3) Install the rear case to the wall, box, etc. with 2 screws
(M4 × 16 mm). Fix the 2 screws in either horizontal or
vertical position.
A. When mounting on the box:
• Attach the case after leading the cable.
Box
Rear case
B. When the cable is along the wall:
• Mount the rear case on the wall.
• Cut off a hole for cabling in the front case.
9380222002-02_IM.indb 5
Unit : mm (in.)
1. 12V (Red)
2. Signal (White)
3. COM (Black)
Rear case
Front case
Remote controller cable
Screws
Cut off
Front case
CAUTION
• When connecting the remote controller cable, take
measures to prevent the water or insects coming into the
remote controller through the cable, such as to provide
the trap or close the hole for cabling with the putty.
Putty
Putty
Trap
(4) Setting up the DIP switch. Refer to [5.4. Setting the DIP
switch].
(5) Connect the cable to the terminals on the front case. Fix
the cable together with the sheath with the binder. Cut off
the excess binder.
Tightening torque
Terminal screw
0.8 to 1.2N • m (7 to 10 lbf • in)
1. 12V (Red)
2. Signal (White)
3. COM (Black)
Binder
Remote controller
cable (sheath)
Good
2 mm
(3/32 in.)
No good
CAUTION
• Be careful to avoid breaking the cable by over-tightening
the binder.
• When connecting the remote controller cables, do not
over-tighten the screws.
Trap
Putty
Trap
Hole for binder
No good
En-5
24/08/2010 10:22:34

Capítulos

Tabla de contenido
loading

Tabla de contenido