3. Specifications
•
Measuring range and accuracy
Function
Earth
resistance
(Auto-ranging)
AC current (ACA)
(sine wave)
(50Hz/60Hz)
(Auto ranging)
* Crest factor <2.5 Accuracy at sine wave +1% (50Hz/60Hz, peak value shall not exceed 60A)
* In the following cases, zero will be displayed on the LCD.
At 20Ω range of Earth resistance function: 0.04Ω or less
* Auto ranging shifts to upper range when the input exceeds 105% of the selected range, and shifts to the lower range when the input
falls under 80% of the lower range.
•
Operating system
•
Display
•
Over-range indication "OL" is displayed when input exceeds the upper limit of a measuring range
•
Response time
•
Sample rate
•
Location for use
•
IP protection degree
•
Temperature &
humidity range
(guaranteed accuracy)
•
Operating temperature 14°F ~ 104°F/Relative humidity 85% or less
& humidity range
•
Storage temperature
& humidity range
•
Power source
•
Current consumption Approx. 50mA (max. 100mA)
•
Measurement time
•
Auto power-off
Range
Resolution
20Ω
0.01Ω
200Ω
1200Ω
100mA
0.1mA
1000mA
10A
0.01A
30A
Earth resistance function: Constant voltage injection, Current detection,
AC current function: Successive Approximation (True-RMS)
Liquid crystal display with a maximum count of 2099
Earth resistance function: Approx. 7 seconds
AC current function:
Approx. once per second
Altitude 2000m or less, Indoor/ outdoor use
IP40
75°F±5%/Relative humidity 85% or less
(no condensation)
(no condensation)
-4°F ~ 140°F/Relative humidity 85% or less
(without batteries, no condensation)
(4) batteries AA
Approx. 12 hours (when manganese battery is used),
Approx. 24 hours (when alkaline battery is used)
Turns power off after 10 minutes of non-use.
Measuring range
0.00
16.0
0.1Ω
100.0
160
1Ω
400
10Ω
600
0.0
1mA
80
0.80
0.1A
8.0
(Frequency: Approx. 2400Hz)
Dual Integration
Approx. 2 seconds
Page 6
~
20.99Ω
~
99.9Ω
~
209.9Ω
~
399Ω
~
599Ω
~
1260Ω
~
104.9mA
~
1049mA
~
10.49mA
~
31.5AmA
Accuracy
±1.5%±0.05Ω
±2%±0.5Ω
±3%±2Ω
±5%±5Ω
±10%±10Ω
—
±2%±0.7mA
±2%