An automatic function of the converter that detects
current consumption while the motor is running. The
converter cuts out the power supply to the motor and
remains locked.
Troubleshooting:
• The motor is damaged and must be replaced.
• The power cable of the motor is faulty or worn:
replace the cable.
Text on
Model
the dis-
14
play (
)
A8
OVER
MMW
VOLT
MTW
MMA
MTA
An automatic function of the converter that detects
the voltage value of the power line. The converter
stops the electric pump when the voltage value ex-
ceeds the permitted limit (254 V). The pump auto-
matically starts up when the voltage drops below the
limit (chapter 2.5).
Troubleshooting:
• Problems with the power line: contact the utility
provider.
• For systems with more than one pump, the elec-
tric pump with converter acts as a current gener-
ator when the non-return valve of the hydraulic
system is faulty. The water flows through the
non-return valve in the opposite direction.
• The DC Bus power circuit of the converter is faul-
ty.
Text on
Model
the dis-
14
play (
)
A9
UNDER
MMW
VOLT
MTW
MMA
MTA
An automatic function of the converter that detects
the voltage value of the power line. The converter
stops the electric pump when the voltage value is
below the permitted limit (184 V). The pump auto-
42
Descrip-
Reset
tion
locked if
the alarm
perse-
veres af-
ter the
reset
tests.
Descrip-
Reset
tion
Alarm in-
Automat-
dicating
ic
the volt-
age sup-
ply of the
converter
is high
Descrip-
Reset
tion
Alarm in-
Automat-
dicating
ic
that the
voltage
supply of
the con-
verter is
too low
matically starts when the voltage exceeds the limit.
See
Technical data
on page 27.
The alarm appears correctly moments before shut-
down.
Troubleshooting:
• The cross-section of the power cable for the con-
verter is too small. Replace the cable with one of
a suitable cross-section taking into account the
voltage drop at the supply point of the converter.
• The power cable for the converter is too long.
Replace the cable with one of a wider cross-sec-
tion taking into account the voltage drop at the
supply point of the converter.
7 System Setup and
Operation

7.1 Parameters to check upon startup

Check the following programming parameters upon
startup:
Display for
Display for
MMW and
MMA and MTA
MTW
A
NOM.CURR
EL
EXT.LOW WA-
TER
SP
SET PRESS
Description
Enter the rated
current value of
the motor indi-
cated on the da-
ta plate.
Entering the in-
correct value
can result in
damage to the
electric pump or
trigger an unan-
ticipated over-
current alarm. If
the length of the
motor's power
cable is ≥30m,
refer to
Applica-
tions with very
long cables
on
page 32.
If there is a level
sensor, enable
control at the
digital input to
protect against
dry running. The
pump restarts
automatically
when the mini-
mum operating
limit is reached.
The operating
pressure of the
pump needs to
be set.
If the value en-
tered is not cor-
rect in relation
to the needs of
the system, it
must be in-