4-WIRE CONNECTION WITH A
POWER SUPPLY CORD
WARNING
• Only a 4-conductor power-supply cord kit rated
120/240 volts, 50 amperes and marked for use with
ranges, with closed loop connectors or open-end
spade lugs with upturned ends, shall be used. The
middle (neutral) wire of the power cord or 4-wire
conduit must be connected to the middle post of
the main terminal block. The other two wires of
the power cord or conduit must be connected to
the outside posts of the main terminal connection
block. The 4th ground wire must be connected to
the frame of the range with the ground screw.
− Failure to do so can result in electrical shock,
severe personal injury or death.
Follow the instructions under "CONNECT RANGE CORD"
on page 7 to correctly install the strain relief.
1. Remove the lower 3 screws from the terminal block and
retain them. (Refer to Figure 9.)
2. Remove the ground screw and bend the end of the
ground strap up so the slot is over the hole of the center
screw removed in step 1.
3. Insert the ground screw into the power cord ground wire
terminal ring and secure it to the range frame.
4. Insert the 3 screws through each power cord terminal
ring and into the lower terminals of the terminal block.
Make sure that the center wire (white/neutral) is
connected to the center lower position of the terminal
block.
Tighten the 3 screws securely into the terminal block. The
center screw now attaches the bent up ground strap to
the block.
5. Go to page 11.
4-wire connection
Black White Red
Conduit
Ground screw
connection plate
FIGURE 9
Terminal
block
Ground strap
Bend strap up and
attach
ELECTRICAL CONNECTIONS
3-WIRE CONNECTION: CONDUIT
Install the conduit as follows:
Remove the conduit connection plate from the rear of lower
oven and rotate it as shown in Figure 5. The conduit hole
(1
/
") must be used.
1
8
First, prepare the conduit wires as shown in Figure 10.
3 wire
Conduit
connection
plate
FIGURE 10
Second, install the conduit strain relief as shown in Figure 6.
For conduit installations, purchase a strain relief and insert
it into the 1 1/8" (2.8 cm) conduit hole. Then install the
conduit through the body of the strain relief and fasten the
strain relief with its ring. Reinstall the bracket.
For conduit connections :
If the wire in the conduit is copper it must be 8 or 10 AWG
wiring.
If the wire in the conduit is aluminum it must be 6 or 8
AWG wiring.
1. Loosen the lower 3 screws from the terminal block. (Refer
to Figure 11.)
2. Insert the bare wire (white/neutral) end through the
center terminal block opening.
Do not remove ground strap connections.
3. Insert the two side bare wire ends into the lower left and
the lower right terminal block opening.
Tighten the 3 screws securely into the terminal block.
(approximately 35 - 50 IN-LB)
4. Go to page 11.
3-wire connection
Black White Red
Conduit
connection plate
FIGURE 11
9
4 wire
Ground
wire
or
Terminal
block
Wire ends