7 Selecting functions

1 ON -
Automatic closing - the automatic closing timer is activated when on opening the gate leaf has reached the full open stroke.
The time is preset and adjustable, and is subject to the action of any safety devices. It does not activate after a total safety
"stop" or during a power outage;
2 ON -
"Open-stop-close-stop" function with button [2-7] and remote control (with built-in radiofrequency card);
2 OFF -
"Open-close" function with button [2-7] and remote control (with built-in radiofrequency card);
3 ON -
"Open only" function with button [2-7] and remote control (with built-in radiofrequency card);
4 ON -
Pre-Flashing during opening and closing - Following an opening or closing command, the flasher connected to [10-E],
flashes for 5 seconds before initiating the operation;
5 ON -
Obstacle detection - When motor is idle (gate closed, open or after a total stop command), it prevents any motion if the
safety devices (e.g. photocells) detect any obstacle;
6 ON -
Maintained action - the gate works by keeping the button pressed (one button [2-3P] for opening, and one button [2-7] for
closing);
7 OFF -
Reopening during closing - if the photocells detect an obstacle during gate closing, the gate motion is inverted until total
opening is reached; connect the safety device to terminals [2-C1); sif not used, set DIP switch to ON;
8 OFF -
Partial stop - stops gate when an obstacle is detected by the safety devices; once the obstacle is cleared, the gate remains
still or closes if the automatic closing function is enabled. Connect the safety devices to terminal [2-C3); sif not used, set DIP
switch to ON.
9 ON -
Operation of the photocells safety test - this allows the card to assess the efficiency of the safety devices (photocells) after
each opening and closing command;
10 ON -
Reaction time - Increases to 2" the running time of the movement inversion function, controlled by the amperometric sensor.
NB – Dip switches 1 through 6 are used, independently, also for the gearmotor and electroloc connection options (pages 7-8-9).
8 Trimmers adjustment
- «SPEED SENS.»
Adjusts the amperometric sensitivity which controls the power developed by the motor during motion; if the
power exceeds the adjusted level, the system sets in motion to invert the direction of motion.
- «SLOW.SENS.»
Adjusts the amperometric sensitivity which controls the power developed by the motor during slowing downs; if
the power exceeds the adjusted level, the system sets in motion to invert the direction of motion.
- «DELAY 2M»
Adjustes the waiting time of the second motor during each closing run. The waiting time can be adjusted
anywhere between 1 and 17 seconds.
- «AUTOM. CLOSING» Adjusts the waiting time when gate is open. Once this time has elapsed, the gate closes automatically. The
waiting time can be adjusted anywhere between 1 and 150 seconds.
DIP-SWITCH
ON
OFF