Safety
Rating Data
Information
4.
Electrical Installation
Always apply control voltage before (or with) mains voltage.
WARNING
Always follow the specified tightening torque for all power and ground terminal connections.
WARNING
All Digistart CS starters include an internal bypass relay that bypasses the soft starter SCRs during run. This
allows the Digistart CS to be installed in a non-ventilated enclosure without an external bypass contactor.
4.1
Terminal layout
For technical data details, see Technical Data on page 17.
4.1.1 Power terminations
Figure 4-1 Cable sizes and maximum torque settings
10 - 35
(8 - 2)
mm 2 (AWG)
10 - 35
(8 - 2)
mm 2 (AWG)
Torx (T20)
3 Nm
2.2 f t -lb
7 mm
3 Nm
2.2 f t -lb
4.1.2 Ground terminal
All Digistart CS soft starters have one ground terminal at the bottom of the starter.
Table 4-1 Ground terminal maximum torque settings
Model
CS1x018 to CS1x060
CS2x085 to CS3x200
Digistart CS User Guide
Issue: 2
Mechanical
Electrical
Installation
Installation
L1/1, L2/3, L3/5, T1/2, T2/4, T3/6
018 ~ 060
075 ~ 100
25 - 50
(4- 1/0)
mm 2 (AWG)
25 - 50
14
(4- 1/0)
(0.55)
mm 2 (AWG)
mm (inch)
mm (inch)
Torx (T20)
4 Nm
2.9 f t -lb
7 mm
4 Nm
2.9 f t -lb
Terminal size
www.controltechniques.com
Programmable
Diagnostics
Parameters
CSH, CSL, CSR, DI1, DI2, TH1, TH2,
140 ~ 200
11
N.A.
(0.43)
26
Ø 8.5
(1.02)
(0.33)
14
N.A.
(0.55)
mm (inch)
N.A.
N.A.
3.5 mm
N.A.
0.5 Nm max
4.4 in-lb max
4 mm
6 mm
Technical Data
Options
COM1, RLO1, COM2, RLO2
018 ~ 200
0.14- 1.5
(26 - 16)
mm 2 (AWG)
0.14- 1.5
6
(26 - 16)
(0.24)
mm 2 (AWG)
mm (inch)
Maximum Torque
2 Nm
3 Nm
9