Mechanical Installation; Dimensions And Weights - Emerson CS Serie Guia Del Usuario

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 83
Safety
Rating Data
Information
3.

Mechanical Installation

Models CS3x140 to CS3x200 are intended to be mounted in an enclosure which prevents access
except by trained and authorised personnel, and which prevents the ingress of contamination. The
WARNING
complete range is designed for use in an environment classified as Pollution Degree 3 in
accordance with IEC60664-1. This means conductive pollution or dry, non-conductive pollution
which becomes conductive due to condensation is acceptable.
Models CS3x140 to CS3x200 can be installed with optional finger guards, in which case they do
not need to be mounted in an enclosure.
3.1

Dimensions and weights

Figure 3-1 Unit dimensions
A
B
C
D
A
Model
mm
(in)
CS1x018
98
CS1x042
(3.9)
CS1x060
CS2x085
145
(5.7)
CS3x140
202
CS3x170
(8.0)
CS3x200
Digistart CS User Guide
Issue: 2
Electrical
Mechanical
Installation
Installation
B
C
D
mm
mm
mm
(in)
(in)
(in)
82
203
188
(3.2)
(8.0)
(7.4)
124
215
196
(4.9)
(8.5)
(7.7)
160
240
204
(6.3)
(9.5)
(8.0)
www.controltechniques.com
Programmable
Diagnostics
Parameters
E
F
C
E
F
mm
mm
(in)
(in)
168
55
(6.6)
(2.2)
196
-
(7.7)
217
-
(8.5)
Technical Data
Options
H
H
G
G
H
Weight
mm
mm
kg
(in)
(in)
(lb)
90.5
23
2.1
(3.6)
(0.9)
(4.6)
110.5
37
4.1
(4.4)
(1.5)
(9.0)
114.5
51
6.5
(4.5)
(2.0)
(14.3)
7
Tabla de contenido
loading

Este manual también es adecuado para:

Cs1x018Cs1x042Cs1x060Cs2x085Cs3x140Cs3x170 ... Mostrar todo

Tabla de contenido