Technical Data - Emerson CS Serie Guia Del Usuario

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 83
Safety
Rating Data
Information
7.

Technical Data

Mains supply
Mains voltage (L1, L2, L3)
CSx4xxx ................................................................................... 3 x 200 Vac to 440 Vac (+ 10% / - 15%)
CSx5xxx ................................................................................... 3 x 200 Vac to 575 Vac (+ 10% / - 15%)
Mains frequency (at start) ..................................................................................................... 45 Hz to 66 Hz
Rated insulation voltage .................................................................................................................. 600 Vac
Form designation ................................................................. Bypassed semiconductor motor starter form 1
Control supply
Control voltage (CSL, CSR, CSH) .................................................................. 110-240 Vac (+ 10% / - 15%)
................................................................................................................ or 380-440 Vac (+ 10% / - 15%)
Recommended fuse .........................................................
Current consumption (during run) .................................................................................................. < 100 mA
Current consumption (inrush) ................................................................................................................ 10 A
Inputs
Start (terminal DI1) ................................................................................ Normally open, 150 k  @ 300 Vac
Stop (terminal DI2) .............................................................................. Normally closed, 150 k  @ 300 Vac
Outputs
Main contactor (terminals COM2, RLO2) .............................................................................. Normally open
............................................................................................... 6 A, 30 Vdc resistive / 2 A, 400 Vac, AC11
Programmable relay (terminals COM1, RLO1) ...................................................................... Normally open
............................................................................................... 6 A, 30 Vdc resistive / 2 A, 400 Vac, AC11
Environmental
Degree of protection CS1x018 to CS2x085 ........................................................................................... IP20
Degree of protection CS3x140 to CS3x200 ........................................................................................... IP00
Operating temperature ..................................................................................................... - 10 °C to + 60 °C
Storage temperature .................................................... -25 °C to + 60 °C (to +70 °C for less than 24 hours)
Humidity ......................................................................................................... 5% to 95% Relative Humidity
Pollution degree .............................................................................................................. Pollution Degree 3
Vibration ........................................................................................................ IEC 60068 Test Fc Sinusoidal
.................................................................................................... 4 Hz to 13.2 Hz: ± 1 mm displacement
....................................................................................................................... 13.2 Hz to 200 Hz: ± 0.7 g
EMC emission
Equipment class (EMC) .................................................................................................................... Class A
Conducted radio frequency emission .................................................... 0.15 MHz to 0.5 MHz: < 90 dB (µV)
.............................................................................................................. 0.5 MHz to 5 MHz: < 76 dB (µV)
............................................................................................................ 5 MHz to 30 MHz: 80-60 dB (µV)
Radiated radio frequency emission ..................................................... 30 MHz to 230 MHz: < 30 dB (µV/m)
................................................................................................... 230 MHz to 1000 MHz: < 37 dB (µV/m)
This product has been designed as Class A equipment. Use of this product in domestic environments may
cause radio interference, in which case the user may be required to employ additional mitigation methods
EMC immunity
Electrostatic discharge ............................................................... 4 kV contact discharge, 8 kV air discharge
Radio frequency electromagnetic field ................................................. 0.15 MHz to 1000 MHz: 140 dB (µV)
Rated impulse withstand voltage (Fast transients 5/50 ns) ...................... 2 kV line to earth, 1 kV line to line
Voltage dip and short time interruption ..................................................... 100 ms (at 40% nominal voltage)
Harmonics and distortion .............................................................. IEC61000-2-4 (Class 3), EN/IEC61800-3
Short circuit
Rated short-circuit current CS1x018 to CS2x060 .................................................................................. 5 kA
Rated short-circuit current CS3x085 to CS3x200 ................................................................................ 10 kA
Heat dissipation
During Start ........................................................................................................................ 3 watts / ampere
During Run ........................................................................................................................... 10 watts typical
Approvals
UL / C-UL .......................................................................................................................................... UL 508
CE
....................................................................................................................................... IEC 60947-4-2
CCC .......................................................................................................................................... GB 14048.6
RoHS ........................................................................................... Compliant with EU Directive 2002/95/EC
Digistart CS User Guide
Issue: 2
Mechanical
Electrical
Installation
Installation
www.controltechniques.com
Programmable
Diagnostics
Parameters
1 A continuous (10 A max, 0.01 second surge)
Options
Technical Data
17
Tabla de contenido
loading

Este manual también es adecuado para:

Cs1x018Cs1x042Cs1x060Cs2x085Cs3x140Cs3x170 ... Mostrar todo

Tabla de contenido