Cabinet Installation; Blower Motor Installation - Thermador PH30HWS Manual De Instrucciones

Ocultar thumbs Ver también para PH30HWS:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Cabinet Installation

The hood can be installed under a cabinet by supporting
the hood from the top.
Note: The cabinet must be structurally joined to the wall
studs to support the weight of this hood. Check the
structural integrity of the cabinet/wall before proceeding.
The figure shows the (4) screw holes labeled "K" used for
mounting the hood to the bottom of the cabinet. Make
sure both knockouts have been removed (see "Prepare for
the wire routing" on page 16).
A A
K x4
K x4
9
9
1
1
/
/
"
"
16
16
(40)
(40)
1
7
/
"
16
(179)
(179)
Hood Size
30'' (762 mm)
36'' (914 mm)
42'' (1,067 mm)
48'' (1,219 mm)
54'' (1,372 mm)
60'' (1,524 mm)
1. In the base of the cabinet, drill 1/8'' (3 mm) tap holes
spaced as indicated by Dimension A.
2. Screw in (4) 1" (25 mm) screws (provided with hood)
leaving 1/4'' (6 mm) exposed to hang hood on.
3. If the hood is installed for vertical discharge, refer to
"Vertical Discharge Transition" on page 13 to create
clearance holes for passage of the transition and
conduit.
4. For horizontal discharge, use See "Horizontal
Discharge Transition" on page 13. for the geometry
of the cutout required for clearance of the transition.
5. Hang hood from screws and tighten securely.
6. From inside of hood, insert screws supplied. Drill
through holes, use 5/8'' (16 mm) screws supplied, (1)
on each side and (4) along the front, into bottom of
the cabinet. See screw holes labeled "L" in figure.
L x2
L x2
L
inches (mm)
A
29'' (737 mm)
35'' (889 mm)
41'' (1,041 mm)
47'' (1,194 mm)
53'' (1,346 mm)
59'' (1,499 mm)

Blower Motor Installation

Blower and Circuit Breaker Ratings
Blower
SKU
Remote
VTR630
120
Remote
VTR1030
120
Remote
VTR1330
120
In-line
VTI610
120
In-line
VTI1010
120
Integral
VTN630
120
Integral
VTN1090
120
9 CAUTION
To reduce the risk of fire and electric shock, install this
range hood only with the blowers listed in the
Ventilation Planning Guide.
NOTE: Cutting the plug of the blower will void the
warranty or eligibility for return or exchange.
All blower models are sold separately. Use only
Thermador blowers with these ventilation hoods. See the
Ventilation Planning Guide for recommended blowers.
Contact Customer Service for additional options.
All hood models are rated for 120V AC installed with a
blower listed in the table above, using a 15 amp
dedicated circuit breaker. The VTR1330 blower in
conjunction with a PHxxGWS requires a 20 amp circuit
breaker.
Blower selection will vary based on the volume of air that
needs moved and the length and location of the duct run.
For long duct runs with multiple turns and bends, consider
using a more powerful blower. For the most efficient air
flow exhaust, use a straight run or as few elbows as
possible (refer to "Ductwork Preparation").
Integral Blower Installation
Integral Blower models are integrated into the hood at the
time of installation. Integral Blowers should be installed
after the hood is mounted to the wall.
Breaker
Voltage
Current
Amp
4.2
15
5.7
15
8.5
15 / 20
4.2
15
5.7
15
4.2
15
5.4
15
Page. 17
Tabla de contenido
loading

Este manual también es adecuado para:

Ph36hwsPh48hwsPh36gwsPh42gwsPh48gwsPh54gws ... Mostrar todo

Tabla de contenido