Steam Line Installation Examples

12 (305)
2 (51)
MINIMUM
12 (305)
MINIMUM
RADIUS
12 (305)
MINIMUM
BEFORE
ANY BEND
CONDENSATE
LINE
CONNECT
CONDENSATE
HOSE TO FILL
CUP
Fig. 12. Steam distributor above humidifier (hose).
Measurements in inches (mm).
12 (305)
MINIMUM
RADIUS
12 (305)
MINIMUM
SUPPORT
BEFORE
BRACKETS
ANY BEND
Fig. 13. Steam distributor below humidifier (hose).
Measurements in inches (mm).
CONDENSATE
LINE
SUPPORT
BRACKETS
CONNECT
STEAM
HOSE TO
CYLINDER
12 (305)
MINIMUM
CONDENSATE
TRAP
TO DRAIN
12 (305)
MINIMUM
RADIUS
12 (305)
MINIMUM
BEFORE
ANY BEND
USE FULL SIZE CONDENSATE
TEE AT LOW POINT. SLOPE
LINES UP TO "T" AND
IMMEDIATELY AFTER IT.
HOSE WILL SOFTEN OVER TIME. PROPER SUPPORT IS NECESSARY.
1
M35717
Fig. 14. Steam distributor below humidifier with
obstruction (hose). Measurements in inches (mm).
M35718
Fig. 15. Common steam line installation errors.
9
1
SUPPORT
BRACKETS
OBSTRUCTION
2 (51)
MINIMUM
TO DRAIN
TO DRAIN
CONDENSATE
TRAP NOT 12
(305) BELOW
DISTRIBUTOR
NO
CONDENSATE
TRAP AT
VERTICAL
TRANSITION
STEAM LINE
NOT SLOPED
Measurements in inches (mm).
HM700A1000
12
(305)
12 (305)
MIN.
MINIMUM
M35719
M35720
33-00118EFS—03