salmson SC-Fire Diesel Instalacion Y Puesta En Servicio página 60

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

English
Code
Fault description
E54.1
No bus communication to
charger for battery A
E54.2
No bus communication to
charger for battery B
E54.3
Faulty data transfer from
charger for battery A
E54.4
Faulty data transfer from
charger for battery B
E100.1
Battery fault in battery A
E100.2
Battery fault in battery B
E105.1
Short-circuit in battery A
E105.2
Short-circuit in battery B
E106.1
Cable break in battery A
E106.2
Cable break in battery B
E109.0
Freely configurable fault
E130.0
Lack of fuel
E131.0
Heating fault
E132.0
Low oil pressure
E133.0
Excess motor temperature
E134.0
Starting pinion not engaged
E135.0
Pinion rim interrupted
E136.0
Starts failed
E137.0
Belt break
If the fault cannot be remedied, please
contact your nearest Salmson customer
service point or representative.
60
Causes
Connection to charger for battery
A interrupted
Connection to charger for battery
B interrupted
Faults on the data cable
Faults on the data cable
Battery A defective
Battery B defective
Battery A defective
Battery B defective
Connection to battery A inter-
rupted
Connection to battery B inter-
rupted
Depending on the fault configu-
ration
Fuel below minimum level
Thermostat for the heating has
triggered
Oil pressure switch has triggered
Thermostat for the motor has
triggered
Confirmation from starting pinion
missing
Confirmation from starting pinion
missing
6 unsuccessful start attempts
performed
No tension for generator
Remedy
Check connection
Request customer service
Check connection
Request customer service
Request customer service
Request customer service
Check battery A and replace,
if necessary
Request customer service
Check battery B and replace,
if necessary
Request customer service
Check battery A and replace,
if necessary
Request customer service
Check battery B and replace,
if necessary
Check connection to battery A
Request customer service
Check connection to battery B
Request customer service
Depending on the fault config-
uration
Refuel
Check heating
Check oil level and refill, if nec-
essary
Request customer service
Check cooling water level
Request customer service
Check starter
Check fuse
Request customer service
Check fuse
Request customer service
Request customer service
Check V-belt and replace, if
necessary
Request customer service