Battery Installation - Kidde HD135F Guía De Usuario

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

• When mixing models which have battery backup (1275, 1276, 1285, 1296,
i12040, i12060, i12080, PE120, PI2000, KN-COSM-IB, HD135F, KN-COB-IC,
KN-COP-IC) with models without battery backup, (1235, i12020, KN-COSM-I,
120X, SM120X, CO120X, SL177i) be advised that the models without battery
backup will not respond during an AC power failure.
• The maximum wire run distance between the first and last unit in an intercon-
nected system is 1000 feet.
• Figure 4 illustrates interconnection wiring. Improper connection will result in
damage to the alarm, failure to operate, or a shock hazard.
• Make certain alarms are wired to a continuous (non-switched) power line.
NOTE: Use standard UL listed household wire (as required by local codes) avail-
able at all electrical supply stores and most hardware stores.
FUSE OR CIRCUIT BREAKER
B LACK
RE D
WH ITE
CO NN ECTOR
Smoke
First
Alarm
A larm
FIGURE 4 INTERCONNECT WIRING DIAGRAM
WIRES ON ALARM HARNESS
Black
White
Red

BATTERY INSTALLATION

See MAINTENANCE (section 7) for battery installation.
CAUTION! IF THE BATTERY REMINDER FINGER IS NOT HELD DOWN IN
THE BATTERY COMPARTMENT BY THE BATTERY, THE BATTERY DOOR
WILL NOT CLOSE, THE AC QUICK CONNECTOR WILL NOT ATTACH TO THE
ALARM, AND THE ALARM WILL NOT ATTACH TO THE TRIM RING (SEE
SECTION 7, FIGURE 9).
HD135F
Heat
A dd iti o n al
A larm
Alarm
CONNECTED TO
Hot Side of AC Line
Neutral Side of AC Line
Interconnect Lines (Red Wires) of Other
Units in the Multiple Station Set up
K i dd e
R elay M od ul e
S M120X
Optional
Optional Accessory
Accessory
B LACK
RE D
WH ITE
CO NN ECTOR
Smoke
A dd iti o n al
Alarm
A larm
Tabla de contenido
loading

Tabla de contenido