of alarms shall be spaced and located
within 3 ft (0.9m) of the peak of the
ceiling measured horizontally" (see
figure 3).
• In rooms with open joists or
beams, all ceiling mounted alarms
shall be located on the bottom of
such beams (see figure 2).
• Alarms installed on an open-joisted
ceiling shall have their smooth ceiling
spacing reduced to no more than half
of the listed spacing when measured
at right angles to the solid joist (See
figure 2).

MOBILE HOME INSTALLATION

Modern mobile homes have been
FIGURE 3
designed and built to be energy effi-
cient. Install heat alarms as recom-
mended above (refer to RECOMMENDED LOCATIONS and FIGURE 1).
In older mobile homes that are not well insulated compared to present stan-
dards, extreme heat or cold can be transferred from the outside to the inside
through poorly insulated walls and roof. This may create a thermal barrier
which can prevent the heat from reaching an alarm mounted on the ceiling. In
such units, install the heat alarm on an inside wall with the top edge of the
alarm at a minimum of 4" (10 cm) and a maximum of 12" (30.5 cm) below the
ceiling (see figure 1).
If you are not sure about the insulation in your mobile home, or if you notice
that the outer walls and ceiling are either hot or cold, install the alarm on an
inside wall.
WARNING: TEST YOUR HEAT ALARM OPERATION AFTER RV OR MOBILE
HOME VEHICLE HAS BEEN IN STORAGE, BEFORE EACH TRIP AND AT
LEAST ONCE A WEEK DURING USE.

3. LOCATIONS TO AVOID

• In front of forced air supply ducts used for heating and air conditioning, near
ceiling fans, or other high air flow areas.