UK
N°163 PRO
SANICUBIC 2 Classic
INSTRUCTIONS ONLY FOR QUALIFIED
PROFESSIONAL SPECIALISTS
1
WORK THAT MAY BE REQUIRED
ELECTRICAL INSTALLATION MUST BE CARRIED
OUT BY A PROFESSIONAL ELECTRICIAN
Before carrying out any other types of work, disconnect
ALARM ON APPLIANCE
the Sanicubic Classic from the power supply.
First interventions on the appliance
FAULT
PROBABLE CAUSES
1 – Alarm + general alarm LED
• Faulty detection system
flashing
2 – Alarm + general alarm LED
• Blocked pipe
lit
• Pump blocked or seized
3 – general alarm LED
• The appliance has the follo-
wing problem: blocked pipe,
seized or blocked pump(s)
• The appliance has been
affected by a mains power cut
4 – Alarm + general alarm LED
• Mains power cut
+ yellow mains LED flashing
Second interventions on the appliance
FAULT
PROBABLE CAUSES
The motor does not start but
• faulty electronic board
the MF works
Pumps on constantly
• Outlet pipe blocked
• Discharge head too high
• Faulty detection system
•faulty electronic board
Pumps work intermittently
• Check valves either leak or
are broken
(*) Warning: if pumping height is high, 90° elbows should be avoided.
MO: Manual Over ride
1 6
DISMANTLING
INSTRUCTIONS RESERVED EXCLUSIVELY
FOR QUALIFIED PROFESSIONAL SPECIALISTS
If one of the motors cannot be made
to operate correctly, use of that motor
can be "disabled" by setting the
corresponding switch on the board
(SW1: switches 1 and 2 for motors 1
and 2).
The motor thus "disabled" can be
removed. The unit operates on
the other motor.
REMOVING A MOTOR
The unit beeps to show that it
is no longer under power.
ACTION TO BE TAKEN
• Consult the SFA customer
services
• Make the pumps work (MO
button) in several bursts.
• Consult an SFA approved
engineer
Unclip the cover.
Unscrew the collar
faulty motor (the check valve
Press on one of the two MO
buttons to reset (alarm stops)
stays in place while the motor
is being repaired).
• To stop the alarm, press on
one of the two MO buttons
Check the electrical system
• Consult the SFA customer
services
ACTION TO BE TAKEN
Unscrew the collar
• Consult the SFA customer
Remove the motor power
services
wires
• Unblock the outlet pipe
connector.
• Check the installation (*)
• Consult the SFA customer
services
Clean or change check valves
Remove the screws
the inspection cover.
Use the handle
motor carefully.
Please contact the service
engineer. You can operate the
lifting station in minimum confi-
guration with just one motor.
Remove the screws
the faulty motor from the
1
inspection cover.
16
DISCONNECT THE UNIT FROM THE POWER
SUPPLY (the yellow indicator light must be flashing off).
A
2
16
on the
A
B
C
3
16
.
B
from the screw
C
E
D
4
16
from
D
to lift the
E
F
5
16
of
F
INDICE
01.12
G
6
16
Put the inspection cover back
in place.
Reconnect the discharge pipe.
Use the plug
to close off
G
the motor cable outlet in the
inspection cover. Fix using
the hose clip
.
B
Operations on the electronic
1
board (cf. illustration
)
:
16
set the switch corresponding
motor from ON to OFF:
to the number of the faulty
1 = motor 1
2 = motor 2
In this configuration, the unit
will not switch to "alarm"
status and the electronic
board only powers the motor
remaining in place.
PUTTING THE MOTOR
BACK IN PLACE
Remove the plug
and the
G
inspection cover.
Screw the motor onto the
inspection cover and put the
cover back in place.
3
Reconnect the motor power
Warning:
wires (cf. illustration
).
16
Comply carefully with the
colour code:
Blue wire with the blue wire
Brown wire with the brown
wire
Green wire with the green
wire
White wire with the white
wire
board to ON.
Set the motor switch on the
Reconnect the discharge
pipe.
Connect the unit to the
power supply.
Carry out a complete test
for commissioning (cf.
paragraph
).
11