ANT+:
Antenna hot pin input
CN3:
ENC1 +: Motor 1 Encoder power supply input
ENC1 E: ENC1 Motor 1 Encoder signal input
GND:
Common GND input
MOT1 FCA:
Motor 1 Opening Limit Switch input (NC)
MOT1 FCC:
Motor 1 Closing Limit Switch input (NC)
ENC2 +: Motor 2 Encoder power supply input
ENC2 E: Motor 2 Encoder Signal input
ENC2 GND:
Common GND input
MOT2 FCA:
Motor 2 Opening Limit Switch input (NC)
MOT2 FCC:
Motor 2 Closing Limit Switch input (NC)
TRANSFORMATOR CONNECTIONS
CN5 (1st):
1: 230 V~ Transformer Primary Winding Input
2: 230 V~ Transformer Primary Winding Input
CN4 (2st):
1: Transformer SEC 1 output 11.8V 3.5A
2: Transformer SEC 1 output 11.8V 3.5A
3: Transformer SEC 2 output 25V 0.8A
4: Transformer SEC 2 output 25V 0.8A
7.2 FUNCTIONAL CHARACTERISTICS
7.2.1 AUTOMATIC OPERATION (OPEN/CLOSE):
When either a stored remote or the connected low voltage pushbutton panel is
used to control the gate, operation is as follows: the first command opens the
gate until motor time elapses or until the gate reaches its opening limit position;
the second command closes the gate; if another command is transmitted
before motor time has elapsed or before one of the two limiters has been
reached, the control unit reverses the movement direction during both opening
and closing.
7.2.2 STEP-BY-STEP OPERATION:
When the LED L1 of the main menu is turned on, when either the remote or
the low voltage control pushbuttons are used to control the gate, operation
is as follows: the first command opens the gate until motor time or until the
gate reaches its opening limit position; the second command closes the gate;
if another command is transmitted before motor time has elapsed or before
one of the limit stops has been reached, the control unit stops the movement.
Another command causes the gate to start moving again in the opposite
direction.
7.2.3 STEP-BY-STEP 1 OPERATION:
When the command is activated (LED L1 lit), using both the radio control and
the low voltage push-button panels to operate the gate, the following will occur:
the first command controls the opening until the motor time limit expires or when
the end of the opening stroke is reached, the second impulse commands the
closing of the gate; if a command is sent before the motor time limit expires
or when one of the two limit switches is reached, the control unit always
stops motion both in the opening and closing phases (even if the pause time
has been previously programmed). Automatic closing is not carried out. A
further command determines resumption of motion in the opposite direction.
7.2.4 AUTOMATIC CLOSING:
The control unit can be set up to close the gate automatically without sending
any additional commands.
The selection of this type of operation is described in Pause time programming
mode PAUSE TIME.
7.2.5 PEDESTRIAN OPENING:
The control unit allows, using both the remote control and the Ped input button,
the operation of the Motor no. 1 only, for a programmable time.
7.2.6 SINGLE LEAF:
Despite being utilized in the configuration for a 2-operator gate opener, the
control unit allows the Pedestrian/Single Leaf pushbutton to start exclusively
Operator no.1, in accordance with the programmed stroke.
7.2.7 EMERGENCY STOP INPUT:
The control unit allows the connection of an emergency stop pushbutton
(NC). Pressing this pushbutton irrespective of the current operating mode
38
COMUNELLO ®Copyright 2019 - All right reserved
of the control unit will cause immediate stopping of the gate movement.
An additional gate movement command will be valid provided the emergency
stop input is deactivated and, in any case, the control unit will execute the gate
opening cycle with 5 seconds pre-flashing.
Important Note: Jumper this input if it is not to be used.
7.2.8 PHOTOCELLS:
Photocells can be powered by and connected to the control unit in accordance
with directive EN 12453.
DS1 Input (NC)
Tripping of the photocells during opening is disregarded, while during closing it
causes reversal of the direction of movement.
DS2 Input (NC)
Tripping during opening causes momentary stopping of the gate; once the
safety is freed the control unit resumes the opening movement. Tripping during
closing causes reversal of the direction of movement.
Programmable input DS3 (NC)
Tripping during opening causes reversal of the direction of movement. Tripping
during closing is disregarded.
To allow operation in compliance with EN 13849-1 Category 2 a photocell
test is performed before each movement. In order to perform this test it is
essential to power the transmitter of each pair of photocells on the specific
"Photocells Power and Control" output (outputs 3 and 4 of terminal strip CN2),
while the receiver of each pair must be powered via the "Users Output" (outputs
14 and 15 of terminal strip CN2). The control unit enables the movement only if
the test is passed; if it is not, the control unit inhibits all movements and an alarm
condition is signalled by blinking of all the programming LEDs on transmission
of each command.
Important note: Inputs DS1 and DS2 (NC) are factory bridged. To wire the
photocells, remove the jumpers from the corresponding inputs.
7.2.9 OPENING AND CLOSING LIMIT SWITCHES:
The control unit allows for the connection of N.C. Opening and Closing limit switches.
The intervention in the respective operating phases causes the immediate stop
of the motion with the correspondence between limit switches and Motor 1
and 2.
Important note: Do not jumper these inputs if they are not used.
7.2.10 ENCODER MOTOR 1 AND MOTOR 2:
The control unit allows the connection of an Encoder for each motor. Use of the
Encoders improves the Obstacle Detection function and guarantees improved
precision during execution of the manoeuvre.
Obstacle detection does not work with automatisms without encoder.
7.2.11 INDICATOR LIGHT:
The control unit allows a 24V DC indicator light to be connected to display the
status of the gate opener.
FUNCTIONING
- Light off:
closed
- Light on:
open
- Light flashes slowly: motion when opening
- Light flashes rapidly: motion when closing
7.2.12 OPERATION WITH TIMER:
The control unit allows a timer to be connected in place of the open – close
push-button.
E.g.: at 08.00 am the timer closes the contact and the control unit commands
an opening movement; at 06.00 pm the timer opens the contact and the
control unit commands a closing movement.
From 08.00 am – 06.00 pm at the end of the opening cycle, the control unit
disables the flashing light, automatic closing and the remotes.
7.2.13 ELECTRIC LOCK CONTROL OUTPUT:
The control unit features an output to control a 24V DC 15W max. electric lock.
The command is switched on at each initial opening movement for a period of
2 seconds.